GMC-I Messtechnik GmbH 25
8 Testing of Breaking Requirements for
Overcurrent Protective Devices,
Measurement of Loop Impedance and Determi-
nation of Short-Circuit Current (functions ZL-PE
and IK)
Testing of overcurrent protective devices includes visual inspec-
tion and measurement. Use the PROFITEST INTRO to perform mea-
surements.
Measuring Method
Loop impedance ZL-PE is measured and short-circuit current IK is
ascertained in order to determine if the breaking requirements for
protective devices have been fulfilled.
Loop impedance is the resistance within the current loop (utility
station – phase conductor – protective conductor) when a short-
circuit to an exposed conductive part occurs (conductive connec-
tion between phase conductor and protective conductor). Short-
circuit current magnitude is determined by the loop impedance
value. Short-circuit current IK may not fall below a predetermined
value set forth by DIN VDE 0100, so that reliable breaking of the
protective device (fuse, automatic circuit breaker) is assured.
Thus the measured loop impedance value must be less than the
maximum allowable value.
Tables containing allowable display values for loop impedance
and minimum short-circuit current display values for ampere rat-
ings for various fuses and circuit breakers can be found in the
help texts and in section 19 beginning on page 54. Maximum
device error in accordance with VDE 0413 has been taken into
consideration in these tables. See also section 8.2.
In order to measure loop impedance ZL-PE, the instrument uses a
test current of 3.7 A to 7 A (60 to 550 V) depending on line volt-
age and line frequency. The test has a duration of max. 1200 ms
at 16 Hz.
If dangerous touch voltage occurs during measurement (> 50 V),
safety shut-down occurs.
The test instrument calculates short-circuit current IK based on
measured loop impedance ZL-PE and line voltage. Short-circuit
current calculation is made with reference to nominal line voltage
for line voltages which lie within the nominal ranges for 120 V,
230 V and 400 V systems. If line voltage does not lie within these
nominal ranges, the instrument calculates short-circuit current IK
based upon prevailing line voltage and measured loop impedance
ZL-PE.
Measuring Method with Suppression of RCD Tripping
The PROFITEST INTRO provides users with the opportunity of mea-
suring loop impedance within systems which are equipped with
RCCBs.
The test instrument
generates a direct
current to this end,
which saturates the
RCCB’s magnetic
circuit.
The test instrument
then superimposes
a measuring cur-
rent which only
demonstrates half-
waves of like polar-
ity. The RCCB is no
longer capable of
detecting this mea-
suring current, and
is consequently not tripped during measurement.
Select the Measuring Function
Connection:
Schuko/3-pole
(country specific)
Connection: 2-pole
Note
Loop impedance should be measured for each electrical
circuit at the farthest point, in order to ascertain maxi-
mum loop impedance for the system.
Note
Bias Magnetization
Suppression of RCD tripping by means of bias magneti-
zation with direct current is only possible via a country-
specific measuring adapter, e.g. PRO-Schuko measuring
adapter (Z503K) or the KS-PROFITEST INTRO (Z503L)
for 3-pole measurement (neutral conductor required).
Note
Observe national regulations, e.g. the necessity of con-
ducting measurements without regard for RCCBs in Aus-
tria.
3-Phase Connections
Measurement of loop impedance to earth must be performed at
all three phase conductors (L1, L2, and L3) for the testing of over-
current protective devices at three phase outlets.
Start
t1 t3
Measuring
t2
Operation
RCD Disabled!
t
IF/mA
Suppression of RCCB tripping for RCCBs which are
sensitive to pulsating current
Z
L-PE
25

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Gossen Metrawatt Profitest Intro wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info