T8600D, T8601D AND T8602D CHRONOTHERM
®
IV DELUXE PROGRAMMABLE THERMOSTATS
68-0164—1
18
(continued)
Table 12. Troubleshooting Information.
Symptom Possible Cause Action
Display will not
come on.
Thermostat is not being
powered.
Check for 24 Vac between R and C or W terminals.
If missing 24 Vac:
check if the circuit breaker is tripped—reset the circuit
breaker.
check if the system fuse is blown—replace the fuse.
check if the power switch on the HVAC equipment is in the
Off position—set to the On position.
check wiring between thermostat and HVAC equipment
replace any broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.
Temperature
display is incorrect.
Room temperature display has
been reconfigured.
Enter Installer Setup number 37 and reconfigure the display.
Thermostat is configured for °F
or °C display.
Enter Installer Setup number 14 and reconfigure the display.
Bad thermostat location.
Relocate the thermostat.
Temperature
settings will not
change. (Example:
Cannot set the
The upper or lower temperature
limits were reached.
Check the temperature setpoints:
Heating limits are 40 to 90°F (4.5 to 32°C)
Cooling limits are 45 to 99°F (7 to 35°C) except D model cooling
limits are 48 to 99°F.
heating higher or
the cooling lower.)
The setpoint temperature range
stops were configured.
Check Installer Setup numbers 34 and 35 and reconfigure the setpoint
stops.
Heating will not
come on.
No power to the thermostat.
Setpoint is above room temperature.
Check for 24 Vac between R and C or W terminals.
If missing 24 Vac:
check if the circuit breaker is tripped—reset the circuit
breaker.
check if the system fuse is blown—replace the fuse.
check if the power switch on the HVAC equipment is in the
Off position—set to the On position.
check wiring between thermostat and HVAC equipment
replace any broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.
Heating will not
come on.
Thermostat minimum off time is
activated.
Wait up to five minutes for the system to respond.
System selection is not set to
Heat.
Set system selection to Heat.
Heating setpoint is below room
temperature.
Check heating setpoint. Set heating setpoint to desired temperature.
Cooling will not
come on.
No power to the thermostat.
Setpoint is below room temperature.
Check for 24 Vac between R or RC and C or Y terminals (D models
requires power to R at all times).
If missing 24 Vac:
check if the circuit breaker is tripped—reset the circuit
breaker.
check if the system fuse is blown—replace the fuse.
check if the power switch on the HVAC equipment is in the
Off position—set to the On position.
check wiring between thermostat and HVAC equipment
replace any broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is
activated.
Wait up to five minutes for the system to respond.
Enter Installer Setup number 33. Reconfigure minimum off time (if
required).
System selection is not set to
Cool.
Set system selection to Cool.
Cool setpoint is above room
temperature.
Check cooling setpoint. Set cooling setpoint to desired temperature.
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Honeywell T8600D - Chronotherm IV wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info