INSTRUCTION MANUAL ROOM CLIMATE CONTROL DEVICEGS10.00PRO
SAFETY INSTRUCTIONS AND BASICS
Technical data / Connection diagram
Safety instructions
Power supply:
Connect as stated on the product!
CAUTION!DANGER OF LIFE / RISK OF FIRE AND ELECTRIC SHOCK!
!!!Installation and assembly of electrical equipment must be carried out only by a skilled person!!!
!!!For devices with 24V ACDC
supply voltage following applies:
SELV
Channels (potential-free):
4 switching channels, normally open
Connect the supply voltage/frequency as stated on the product!
Disconnect device from power supply for wiring and installation purposes! Check power supply is disconnected!
After completing the installation the terminal cover MUST be reattached! The device may only be operated with front and terminal cover!
The safety precautions of DIN VDE 0100, electric shock, and fire danger have to be met.
Defective devices / sensors have to be put out of service immediately!
For devices with 24V ACDC supply voltage following applies: The supply voltage must meet the requirements for SELV!
Installation and assembly of electrical equipment must be in accordance with local building and electrical codes!
Warranty void if housing opened by unauthorised person!
Donotuse the sensor for safety-relevant gas measurements!
Switching capacity:
Connect as stated on the product!
Analogue control outputs:
3 x 0-10 Volt
Permitted ambient temperature:
0°…+50°C
Housing:
self-extinguishing thermoplastic
Mounting:
wall mounting
Type of connection:
Screw terminals
Type of protection:
IP 20 to DIN EN 60529
Class of protection:
II when installed according to regulations
Features of actions:
1B
Usage / disposal
The climate control deviceis provided for use in interior andliving areas!
The device includes sensors for measuring and controlling CO
2
concentration, relative humidity and temperature.
The relay switches in according to the set threshold values for CO
2
and relative humidity (example for application: ventilation). Via
analogue control outputs the measured values of the CO
2
concentration, relative humidity and temperature can be output.
The device is to be disposed in an environment-friendly way and according to current law.
ASSEMBLY
Assembly
Disconnect device from power supply for wiring and installation
purposes! Check power supply is disconnected!
Attention! You have to check and consider the safety instructions above!
This deviceis suitablefor wall mounting or for mounting on a flush-mounting box.
The device should not be exposed to air draught or direct sunlight.
Don´t install it curtains, or in niches, or close to heat sources.
The device should not be exposed todusty environment.
Ensure that no dust get inside of this device.
For devices with 24V ACDC supply voltage following applies:
The supply voltage must meet the requirements for SELV!
Afterinitial startup, thedevicerequiresup to 5 minutesuntil the firstcorrect
measurementis possible
Installation note: For an easy mounting and installationyou can unplugthe ribbon cableto remove the front covercompletely. (Ribbon cable: logic cable connection
between front-cover and back-cover). After mounting / installation=>For a proper function of the device youhave to reconnectin the ribbon cable.
STEP 1:Open the deviceat the bottom and remove the front cover!
STEP 2:Remove the terminal cover (shown in grey)!
STEP 3:Mountthe rear cover to the wall or on a flush-mounting box(consider STEP 4)!
STEP 4:Feed the cables through the appropriate cable passages:
Cable passage I:Cables for analogue outputs and GND (Terminal 1,2,3,4)
Cable passageII:Cables for Relay A and Relay B (Terminal 5,6 / 7,8)
Cable passageIII: Cables for Relay C and Relay d (Terminal 9,10 / 11,12)
Cable passageIV:Cablesof the supply voltage (Terminal 13,14,15)
STEP 5:After completing the installation the terminal cover MUST be reattached!
STEP 6:Reattach the front cover!
OPERATION
Settings and functions
Functions
(examine)
Relay Sensors
Threshold
settings
Setting range
(thresholds)
Response to the set thresholdsPermanent switching
Factory
setting
CO
2
concentration
Relay
A
CO
2
[ppm]
Via
Rotary switch
A
700ppm -
1.300ppm
(± 100 ppm)
The relay switches on when exceeding
the threshold
(Hysteresis ± 50 ppm)
Turnrotary switch to left end of scale (Pos.MIN): PERMON
Turnrotary switch to right end of scale (Pos.MAX): PERM OFF
1.000ppm
CO
2
concentration
Relay
B
CO
2
[ppm]No settings possible!
Fixthreshold1400 ppm!
The relay switches on when exceeding
1400 ppm
(Hysteresis ± 50 ppm)
No settings possible!
Humidify
Relay
C
RH [%]
Via
Rotary switch
C
15%RH - 45%RH
(± 3%)
The relay switches on when exceeding
the threshold
(Hysteresis ± 3%)
Turnrotary switch to left end of scale (Pos. MIN): PERM ON
Turnrotary switch to right end of scale (Pos. MAX): PERM OFF
PERM
OFF
Dehumidify
Relay
D
RH [%]
Via
Rotary switch
D
50%RH - 80%RH
(± 3%)
The relay switches on when exceeding
the threshold
(Hysteresis ± 3%)
Turnrotary switch to left end of scale (Pos. MIN): PERM OFF
Turnrotary switch to right end of scale (Pos. MAX): PERM ON
65%RH
LED-display – Relay status
LED-DISPLAY
OFF
LED- DISPLAY
PERMANENT GREEN
LED- DISPLAY
FLASHING GREEN
LED- DISPLAY
PERMANENT ORANGE
CO
2
-LED
Relay A „OFF“
Relay B „OFF“
Relay A „OFF“
Relay B „OFF“
Relay A „ON“ Relay A and/orRelay B „ON“
Permanent OFF setting via rotary switch
(setting via rotary switch A)
Measured value is belowthreshold
(setting via rotary switch A)
Measuredvalueis above threshold
(setting via rotary switch A)
Measured value over 1400 ppmor
Permanent ON setting via rotary switch
(setting via rotary switch A)
CO
2
concentration OK
CO
2
concentration above threshold
CO
2
concentration poor
RH-LED
Relay C „OFF“
Relay D „OFF“
Relay C „OFF“
Relay D „OFF“
Relay C and/orRelay D „ON“
Permanent OFF setting via rotary switch
(setting via rotary switch C or D)
Measured value is below threshold valuefor dehumidifying
Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.
Art des Missbrauchs:
Forenregeln
Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:
Lesen Sie zuerst die Anleitung;
Schauen Sie nach, ob die Frage bereits gestellt wurde;
Stellen Sie die Frage so deutlich wie nur einigermaßen möglich;
Erwähnen Sie was Sie bereits versucht haben um das Problem zu lösen;
Ist Ihr Problem von einem Besucher gelöst dann lassen Sie ihn / sie wissen in diesem Forum;
Falls Sie reagieren möchten, so verwenden Sie bitte das Antworten- Formular;
Da ihre Frage für alle Besucher sichtbar ist, sollten Sie lieber keine persönliche Daten erwähnen.
Neu registrieren
Registrieren auf E - Mails für Hugo Muller GS10.00PRO wenn:
neue Frage gestellt werden
neue Handbücher vorhanden sind
Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.
Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.
Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.
Ihre Frage wurde zu diesem Forum hinzugefügt
Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.