Requirements for chimney and flue duct
The height of the chimney must ensure sufficient draught and prevent any smoke nuisance. As a general rule, satisfactory draught conditions are
achieved if the chimney is 4 m above the stove and at least 80 cm above the ridge. If the chimney is placed at side walls, the top of the chimney
should always be higher than the ridge or the tallest point of the roof. Always be aware of any national and/or local regulations applying to thatched
roofs and the location of the chimneys.
The insert requires a minimum draught of 12 Pa (measured at EN 13240 measurement point). If measured just above the smoke flue socket, the
chimney draught must be 18-20 Pa.
The chimney must have a minimum clearing of Ø 150 mm. The chimney must be provided with an easily accessible cleaning door. The chimney and
flue duct must be of flue class T400 and be CE marked. Furthermore, it must have obtained the classification of G in soot fire testing. The required
distance to combustible material must be complied with in accordance with the brand label. Ask your HWAM retailer for further information.
insTallaTion and connecTion
In general
If the stove is to be connected to a fresh air system (optional accessory), the fresh air system must be built into the floor or wall before the
wood-burning stove is installed. Do not place heat-storing stone (optional accessories) in the heat compartment until the wood-burning stove
has been installed.
A plate can be purchased for weight distribution / reinforcement of the floor (optional accessory), if required due to the weight of the wood-bur-
ning stove and any acquired heat-storing stone.
Installation in rooms with non-combustible material
When installing the wood-burning stove up against a non-combustible wall, there are no requirements on the distance to the back or the side of
the stove. The general distance requirements appear from the illustrations below.
Installation in rooms with combustible material
When installing the wood-burning stove against a combustible wall, the current distance requirement from the combustible wall to the flue duct
must be observed. We recommend looking into the safety distance demands for the chosen flue duct solution before deciding on the final place-
ment of the wood-burning stove.
The minimum distance requirements to combustible materials appear from the chart below and the illustrations on the following three pages.
No. shown in
illustration
Min. distances - insulated flue gas pipe: HWAM 5530
1. To non-combustible wall, back, cm 0
2. To non-combustible wall, side, cm 0
1. To combustible wall, back, cm 0
2. To combustible wall, side, next to the stove, cm 0
2. To combustible wall, corner installation (45º), cm 0
3. Distance to furnishings in front, cm 120
4. To combustible wall, side, in front of the stove, cm 35
5. To fireproof wall, side, in front of the stove, cm 18.5
6.
Length of fireproof wall to the front of the stove, cm
70
7. From floor to combustible ceiling, cm 220
No. shown in
illustration
Min. distances - uninsulated flue gas pipe: HWAM 5530
1. To non-combustible wall, back, cm 0
2. To non-combustible wall, side, cm 0
1. To combustible wall, back, cm 5
2. To combustible wall, side, next to the stove, cm 0
2. To combustible wall, corner installation (45º), cm 0
3. Distance to furnishings in front, cm 120
4. To combustible wall, side, in front of the stove, cm 35
5. To fireproof wall, side, in front of the stove, cm 18.5
6.
Length of fireproof wall to the front of the stove, cm
70
7. From floor to combustible ceiling, cm 220
6

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Hwam 5530 - Smartcontrol wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Hwam 5530 - Smartcontrol

Hwam 5530 - Smartcontrol Installationsanweisung - Deutsch - 32 seiten

Hwam 5530 - Smartcontrol Bedienungsanleitung - Deutsch - 8 seiten

Hwam 5530 - Smartcontrol Bedienungsanleitung - Englisch - 8 seiten

Hwam 5530 - Smartcontrol Installationsanweisung - Holländisch - 32 seiten

Hwam 5530 - Smartcontrol Bedienungsanleitung - Holländisch - 8 seiten

Hwam 5530 - Smartcontrol Installationsanweisung - Französisch - 32 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info