12 V CABLE
The operation of your in-lite system is largely determined by the type of
12 V cable you use and the way in which you lay it. This manual explains
the different types of in-lite cables and the options for installing them.
Please read the following instructions before installing.
You are advised to keep these installation instructions in a safe place.
Although a 12 V system is safe, we advise you to have a qualified
electrician check the installation.
Important!
Never connect the low-voltage cable directly to a 100-240 V power
source. It is only suitable for use in combination with a 12 V low-voltage
system. This product should only be used within the in-lite system. Use of
products other than those made by in-lite will invalidate the warranty.
Enjoy the lighting in your yard.
EN
Types of 12 V cable
There are two types of in-lite cables available: 14/2 and 10/2. The
distance the cable must cross in the garden determines the type of cable
you choose. A heavier cable is needed for longer distances. Therefore
always draw a cable plan first. We recommend you use only one type of
cable in a garden, also if you want to install several transformers (and
therefore make several cable plans for one garden). This will help
prevent mistakes that lead to the system not working correctly.
Options for laying 12 V cable
There are two types of cable plans or methods of laying cables: linear
and split. If you have made a lighting plan then making the wiring
diagram is just a question of drawing the cable onto the garden design.
Follow an imaginary line between the fixtures. Always test the circuit
above ground before you bury the cable underneath paving or soil.
Option 1: linear
Roll out the cable from the transformer into the garden and lead it to
the various armatures. The cable can end anywhere and can have the
following maximum length:
14/2 cable up to 40 m (Fig. 1A)
10/2 cable up to 80 m (Fig. 1B)
Does your lighting plan include fixtures with power greater than 35 W?
Always use the 10/2 cable for these.
Option 2: split
Roll out the cable from the transformer into the garden. Using the cable
connectors, make one or more branches that you lead to the various
fixtures. Ensure that the ridged and the smooth sides of both cables point
in the same direction. (Fig. 3)
The maximum length of the branch or branches depends on the place
where you install the cable connector or connectors. For each branch
first calculate the length of cable from the transformer to the relevant
cable connector. Subtract this length from the maximum cable length for
the cable you are using. The remaining number of metres is the maximum
length of the branch. You can make several branches as long as this total
does not exceed the maximum cable length:
14/2 cable up to 40 m (Fig. 2A)
10/2 cable up to 80 m (Fig. 2B)
Does your lighting plan include fixtures with power greater than 35 W?
Always use the 10/2 cable for these.
Important!
The maximum load of each cable connector is 50 W. If the total power of
the fixtures after the CC-2 is greater than 50 W, then multiple CC-2s must
be fitted. (Fig. 4). Always round up the number of cable connectors to be
used. (Fig. 5). Try to spread the power as evenly as possible along the
cable. This will benefit the light output.
Installation tips
Tip 1
Use plenty of cable for the installation. The cable will not then be under
tension if the garden subsides a little.
Tip 2
Insulate the cable ends with caps. You can do this by pulling the end
three centimetres of cable apart and putting a cap on each end. You do
not need to remove any insulation from the cable.
Tip 3
When connecting the fixtures leave plenty of cable from the fixture.
There are special extension cables (CBL-EXT CORD) of 1 metre and 3
metres available to increase the distance of the fixture to the main cable.
These are easy to install between the mini-connector on the fixture and
the mini-connector on the Easy-Lock (Fig. 6).
If after reading these instructions you have further question about
installing 12 V cable, please contact your dealer.
EN
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für In Lite CBL-120 10-2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info