TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is
designed with a fuse to provide overcurrent
protection. The specifications of the fuse
are printed on the circuit board, such as:
Indoor unit: T5A/250VAC
Outdoor unit(applicalbe to units adpot
R32 or R290 refrigerant only):
T20A/250VAC(<=18000Btu/h units)
T30A/250VAC(>18000Btu/h units)
NOTE: The fuse is made of ceramic.
1.
Prepare the cable for connection:
a.
Using wire strippers, strip the rubber jacket
from both ends of signal cable to reveal
about 40mm (1.57in) of the wires inside.
b.
Strip the insulation from the ends of the
wires.
c.
Using wire crimper, crimp u-type lugs on
the ends of the wires.
PAY ATTENTION TO LIVE WIRE
While crimping wires, make sure you clearly
distinguish the Live (“L”) Wire from other wires.
2. Open front panel of the indoor unit by loosen
the screws according to picture Fig.4.7, which
provide big space for wiring connection.
3.
Open the wire box cover to connect the cable.
WARNING
4. Unscrew the cable clamp below the terminal
block and place it to the side.
5. Facing the back of the unit, remove the plastic
panel on the bottom left-hand side.
ALL WIRING MUST PERFORMED STRICTLY
IN ACCORDANCE WITH THE WIRING
DIAGRAM LOCATED ON THE INSIDE OF
THEINDOOR UNIT’S WIRE COVER.
Terminal
block
Wire
cover
Cable
clamp
Fig. 3.13
The Wiring Diagram is located
on the inside of the indoor unit’s
wire cover.
6. Feed the signal wire through this slot, from
the back of the unit to the front.
7. Facing the front of the unit, match the wire
colors with the labels on the terminal block,
connect the u-lug and and firmly screw each
wire to its corresponding terminal.
CAUTION
DO NOT MIX UP LIVE AND NULL WIRES
This is dangerous, and can cause the air
conditioning unit to malfunction.
8. After checking to make sure every connection
is secure, use the cable clamp to fasten the
signal cable to the unit. Screw the cable clamp
down tightly.
9. Replace the wire cover on the front of the
unit, and the plastic panel on the back.
NOTE ABOUT WIRING
THE WIRING CONNECTION PROCESS
MAY DIFFER SLIGHTLY
BETWEEN UNITS.
Page 19
Step 7: Wrap piping and cables
Before passing the piping, drain hose, and the
signal cable through the wall hole, you must
bundle them together to save space, protect
them, and insulate them.
1. Bundle the drain hose, refrigerant pipes, and
signal cable according to Fig. 3.14.
Indoor Unit
Space behind unit
Refrigerant piping
Drain hose
Signal wire
Insulation tape
DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom
of the bundle. Putting the drain hose at the
top of the bundle can cause the drain pan
to overflow, which can lead to fire or water
damage.
DO NOT INTERTWINE SIGNAL CABLE WITH
OTHER WIRES
While bundling these items together, do not
intertwine or cross the signal cable with any
other wiring.
2. Using adhesive vinyl tape, attach the drain
hose to the underside of the refrigerant pipes.
3. Using insulation tape, wrap the signal wire,
refrigerant pipes, and drain hose tightly
together. Double-check that all items are
bundled in accordance with Fig. 3.14.
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends
of the piping unwrapped. You need to access
them to test for leaks at the end of the
installation process (refer to
Electrical Checks
and Leak Checks
section of this manual).
Step 8: Mount indoor unit
If you installed new connective piping to the
outdoor unit, do the following:
1. If you have already passed the refrigerant
piping through the hole in the wall, proceed
to Step 4.
2. Otherwise, double-check that the ends of the
refrigerant pipes are sealed to prevent dirt or
foreign materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant
pipes, drain hose, and signal wire through the
hole in the wall.
4. Hook the top of the indoor unit on the upper
hook of the mounting plate.
5. Check that unit is hooked firmly on mounting
by applying slight pressure to the left and
right-hand sides of the unit. The unit should
not jiggle or shift.
6. Using even pressure, push down on the
bottom half of the unit. Keep pushing down
until the unit snaps onto the hooks along the
bottom of the mounting plate.
7. Again, check that the unit is firmly mounted
by applying slight pressure to the left and the
right-hand sides of the unit.
Fig. 3.14
19

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Inventor P9VO32 Passion Eco wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Inventor P9VO32 Passion Eco

Inventor P9VO32 Passion Eco Zusatzinformation - Deutsch - 60 seiten

Inventor P9VO32 Passion Eco Bedienungsanleitung - Deutsch - 76 seiten

Inventor P9VO32 Passion Eco Zusatzinformation - Englisch - 24 seiten

Inventor P9VO32 Passion Eco Zusatzinformation - Englisch - 60 seiten

Inventor P9VO32 Passion Eco Bedienungsanleitung - Englisch - 76 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info