Warning: Should the terminals/poles be wrongly connected to the load output, can units <10A (fused) be completely damaged. Each
individual component must be fused.
Pre-installation
Upon delivery is the solar charger unit installed as follows:
- Gas control active (see functions)
The above functions can be turned off at any time.
De-activate as follows:
Gas control de-activate
1. Unscrew the 2 screws on the left side (see diagram) on the solar charger unit and carefully remove the casing/lid.
2. Disconnect the jumper J6 situated to the electronic-base. The gas control is now de-activated.
Installation - Warning: Take care that the Terminals/Poles correspond!!!
The solar charger unit should be placed proximity to the battery and be sufficiently protected against the weather. Take care to place the battery
in a well ventilated place. To enable the unit to function properly, the electrical connections should face downwards. To guarantee that the unit
functions properly it must be connected to the solar generator, the lead-battery and the load.
Each part of the system-solar generator, lead battery, load and solar charger unit should have the corresponding power supply. Please check
each component before installation, when in doubt contact a Specialist! Take careful attention of the following installation instructions:
1. Connect the battery to the corresponding terminals on the solar charger unit. To prevent the wiring from overheating and power supply
reduction the use of cable/wire 2,5-4 mm² flexible is recommended. Only when a "short-circuit-protection" connection is installed, can the
battery be operated without a fuse. Otherwise must a fuse be connected to the battery +terminal/pole in order to prevent the connection to
the solar charger unit from "short-circuiting". Both components must be installed close together in the same room.
2. Connect the solar cell to the corresponding terminals on the solar charger.
3. Connect the load to the solar charger unit.
The connection-terminals pictured on the solar charger unit or see diagram (Connection/Operating-elements).
The Solar System fails to Function - possible reasons.
Battery poles: Glass fuse is melted; replace by same type.
Module terminals/poles are wrongly connected: Avoid at all costs!!!
Load terminals/poles are wrongly connected: The apparatus can be seriously damaged before the fuse blows. Batteries contain considerable
amounts of electrical energy. A short-circuit can result in a large build-up of heat leading to FIRE!!
LED
green
LED
red
During the day At night Additional note
1 OFF OFF No flow of charging current Deep discharge not active
No flow of
charging current
Module poled;
Consumer short-circuit
Check flat fuse Check flat fuse Remove cause of defect
Load does not work although fuse
o.k.
Charge control defect.
2 ON OFF Flow of charge current
Battery is charging
The green LED reduces luminous intensity
when reaching the charging limit
Strong light of green LED Charge control defect
3 OFF ON Battery empty Load disconnection active
Consumer switched off
No flow of charging current Check poles, interruption
4 ON ON Battery empty
Flow of charge current
Load is automatically switched on after
reaching the minimum charge
Specifications
Nominal voltage:
Charging current (solar cells):
max. load:
max. power use:
Temperature sensor:
Final charging voltage:
normal
gassing deactivated
temperature compensation
Over discharge disconnection:
constant
reset voltage
Gas regulation:
gassing activation voltage
final gassing voltage
temperature compensation
Fuse:
Temperature range:
Measurements:
Weight:
12/24 V
8 A
8 A
2 mA
in-built
13,7 V / 27,4 V
14,1 V / 28,2 V
-4 mA/K/cell
11,1 V / 22,2 V
12,6 V / 25,2 V
12,4 V / 24,8 V
14,5 V / 29 V
-3 mA/K/cell
10 A
-25°C - +50°C
95 x 95 x 35 mm
230 g
Subject to technical alternation. No responsibility will be taken for Printing mistakes. 05/2009
IVT Innovative Versorgungs-Technik GmbH, Dienhof 14, D-92242 Hirschau
Phone: (49) 96 22 - 719910, Fax: (49) 96 22 – 7199120 www.IVT-Hirschau.de Info@IVT-Hirschau.de
www.busse-yachtshop.de | info@busse-yachtshop.de
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für IVT 8A Solar wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info