554872
1
Zoom out
Zoom in
Gas leak detector GS-130
The GS-130 detects all mixtures of air and combustible gas (Natural Gas, Me-
thane, Propane, Butane, GPL, etc). The detector detects two levels of gas con-
centration - different output reactions.
The main GS-130 features are: high reliability and sensitivity, compact size,
230V (110V optional) power supply and long stability & lifetime.
Installation
A professional installer should install the
detector. (recommended in compliance
with EN 50244).
Fix the detector on the
wall. For gases lighter than
air (natural gas, city gas etc.)
install it close to the ceiling
(max. 15 cm under it) or
directly on the ceiling and on
the place expected to have
gas leakage. For gases
heavier than air (propane,
butane, etc.) install it close to
the floor or on the lowest
place of the room. The
detector should not be
located close to any obsta-
cles preventing natural air
circulation.
Memory
The memory function is disabled by factory default (when the concentration of
the gas drops down to normal, the GS-130 will stop the alarm signal).
Close the MEM jumper to select the memory function. Then the alarm indica-
tion, if triggered, will not stop unless the GS-130 power supply is terminated for a
while.
Power supply
Connect the power cord to the terminals marked 230V AC (or 110V AC). The
power inlet should be fused with an external fuse (max. 10A).
Output relay function
There is a dry relay contact available on the GS-130 output terminals:
C - common contact
NO - normally open contact
NC - normally closed contact
This relay output can be used for an automatic gas-valve closer, alarm system
triggering or for other warning systems.
When the automatic gas-blocking function is used, the application of this shall
be according to national regulations and EN 1775.
If the REL jumper is open, the relay will be triggered after the 1st level of gas
concentration is detected. If the REL jumper is closed, the relay will be triggered
after the 2nd level of gas concentration is detected.
green LED
red LED
NO 230V
JABLOTRON
GS-130
REL
AUX
MEM
C ACNC
buzzer sensor
Fig. 2
red LED
Function
After switching the power on, the green LED will flash for 60 sec. (the detector
warms up). When the green indicator lights permanently the detector is ready.
If the gas concentration reaches the 1st level, short beeps will sound and red
LED I will go off.
If the gas concentration reaches the 2nd level, long beeps will sound and red
LED II will go off.
The output relay reacts depending on the REL jumper setting.
Warning - in the case of a gas alarm stay calm and act as follows: - do not
operate any switches
- do not use any kind of phone in the location of the gas leakage
- open any windows
- stop the gas leakage if possible or leave the place and call the gas
supply company
Warning leaking gas can be smelled before the detector detects an
alarm-level concentration of gas. In this case, the cause of the gas
leak should be eliminated immediately.
Maintenance and testing
Keep the detector clean, it is important that its grids should not be blocked with
dust.
Use a gas cigarette lighter without the flame lit, to test the gas detector’s reac-
tion. The detector will react within 15 seconds.
Professional recalibration of the detector should be done at least once a
year. Contact your distributor for more details.
LED indicators
Green
OFF
Flashes
ON
The detector is off
Warming up
Ready for gas alarms
Red I.
ON
1
st
level of the gas concentration
Red II.
ON
2
nd
level of the gas concentration
Red II.
Green
Alternating
flashes
Error in the sensor
Specification:
Sensitivity (gas concentration):
Methane
Level 1
10
±
3% LEL (0.50% vol.conc.)
Level 2
18
±
3% LEL (0.80% vol. conc.)
Iso-butane
Level 1
23
±
3% LEL (0.30% vol. conc.)
Level 2
40
±
3% LEL (0.50% vol. conc.)
LEL = Lower Explosive Limit (100 %) according to EN 60079-20-1: for
methane 4,4 % vol. conc., for prophane 1,7 % vol. conc., for iso-buthane
1,3 % vol. conc., calibrated by iso-butane
Power supply 230V(-15% to+10%) / 50Hz, 2 W, protection class II
Detection method hot platinum filament
Buzzer sound level 94dB/0.3m
Relay output optional for 1st or 2nd level, max. 230V AC/5A
Alarm memory selectable
Response time 20 s
Warm up time approximately 90 s
Working environment indoor use, -10 to +40°C, IP30
Working humidity max 80 %
designed to operate at normal atmospheric pressure 86 to 106kPa
Complies with EN 50194-1, EN 60079-29-1, EN 50130-4,
EN 55022, EN 60950-1
For non-explosive areas. Zone 2 according to EN 60079-10.
Certified by VVUÚ corp., certificated body No. 3076, by FTZÚ corp., certifi-
cated body No. 3051
Complies with the essential requirements of: 2006/95/EC Low
Voltage Directive - Health and safety protection, 2004/108/EC
EMC Directive concerning electromagnetic compatibility and
2011/65/EU RoHS when used for its intended purpose. The
original of the conformity assessment can be found at
www.jablotron.com, Technical Support section.
Note: Although this product does not contain any harmful materi-
als we suggest you return the product to the dealer or directly to
the producer after use.
ready
green
red
1st level
2nd level
Fig. 1
OK
I.
II.
red
Gas Leak Detector GS-130 2/2 MEF51016

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Jablotron GS-130 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info