554792
9
Zoom out
Zoom in
Vorherige Seite
1/22
Nächste Seite
3 7 1 Sirens always sound during audible alarms
3 7 0 Sirens only sound during audible alarms when all
sections are set, i.e. no one is at home
Factory default setting: Sirens always sound during audible alarms.
JA-82K control panel installation manual - 9 - MKH51103
6.20 Wireless siren alarm enabled (IW and EW)
This setting is for enabling and disabling wireless sirens in the system:
3 8 1 wireless sirens enabled
3 8 0 wireless sirens disabled
Note: This setting applies both to internal and external wireless sirens.
Factory default setting: wireless sirens enabled
6.21 Bypass user approval
This setting can change the function of the system when it is being set
(armed) and if there is:
any detector triggered
any tamper alarm
any trouble in the power source
lost communication with any wireless device (for more than 20
minutes)
any panic button triggered
If bypass user approval is set (391), then during setting (arming), the
system notes which problems mentioned above are active and displays
informative text on the keypad and only bypasses them if the user approves
the bypassing by keying in a within 6 seconds of being notified.
The system has a built-in auto-bypass function (setting 390) so that if any
number of detectors are being triggered during setting (arming) then they will
be bypassed and ignored automatically without consulting the user.
3 9 1 Approval by pressing the key is requested from the
user
3 9 0 Bypassing occurs automatically without user approval
Notes regarding setting the system with (a) triggered detector(s) or
problems as mentioned above:
Details can be viewed by pressing the ? key (e.g. open doors or
windows).
If a wireless keyfob is used to set the system and auto-bypass user
approval is enabled, the system will set without bypass approval, i.e.
setting by keyfob does not trigger an approval request.
The automatic bypass of a detector will end after the detector has been
de-triggered (for example if a door is closed) or the problem
disappears.
If auto-bypass user approval is enabled and Service mode is being
exited while a detector is being triggered, the installer will be notified
about the bypass. The installer can then approve the bypass by
pressing # twice.
To comply with the EN-50131-1, 3 standards 391 should be set.
Factory default setting: Bypassing occurs automatically without user
approval.
6.22 Final-door detectors
In this mode, up to 5 detectors can be defined as final-door detectors and
assigned to addresses 01 to 05 or 46 to 50 in order to make leaving a
building much easier, especially via a garage:
6 5 x
Where x = 0 none,
x = 1 detectors on addresses 01 to 05,
x = 2 detectors on addresses 46 to 50.
Description of final-door detector mode:
If a final-door detector is used in the system then the value of x for exit
delay programming is multiplied by 30 s (see 12) thereby extending the
delay, and if an entrance delay is triggered by a final-door detector then
the value of x for the entrance delay is also multiplied by a larger value
of 30 s.
A final-door detector should be programmed to have a natural reaction,
otherwise it works as it is set (e.g. instant reaction).
Only door/window detectors, hard-wired control panel inputs or hard-
wired inputs in the wireless keypad unit to whose alarm input the final-
door detector is connected should be assigned to the addresses which
you set with this sequence as belonging to final-door detectors.
If a final-door detector is used for a garage door, no instant detectors
should be inside the garage. Next-delay detectors would however be
acceptable.
Setting (arming) the system with a final-door detector:
After entering a request to set the system, an exit delay of between 30
to 270 seconds will begin and be indicated.
If a final-door detector is triggered during the exit delay, the exit delay
will be extended by the time in which the detector is still triggered. So, if
for example, the door is left continuously open, the exit delay will never
end.
If a final-door detector is de-triggered, the system will wait five more
seconds during which beeping gets faster, and if the door is not
opened again during this short period, the exit delay will terminate and
the system will be set immediately.
The duration of the exit delay therefore depends on the time the final
door stays open. For instance, in winter if the driveway in front of a
garage needs to be cleared of snow there will be plenty of time to do it,
and in summer when garages can be exited easily and therefore
quickly, the exit delay can be rather shorter. The exit delay only
depends on the length of time the garage door is left open.
If no final-door detectors are triggered during the exit delay, the system
will provide an exit delay and then set.
If the final door detector stays continuously triggered, an endless exit
delay will result with the system never being set. This means all
delayed and next-delayed detectors will not be set (armed).
If there are multiple final-door detectors in the system, the exit delay is
extended if any of them is triggered and ends after all final-door
detectors have been de-triggered.
Unsetting (disarming) the system with a final door detector:
If a final-door detector gets triggered in a set (armed) system, an
entrance delay will begin with a duration of between 30 and 270
seconds.
If a normal delayed detector gets triggered while the user enters a
building, the system starts an ordinary entrance delay of between 5
and 45 seconds.
If a final-door detector is triggered first, a longer entrance delay will
begin. If during this delay an ordinary delayed detector is then
triggered, the remaining entrance delay will then be shortened to the
delay associated with detectors of this kind.
Note: Only use status-reporting detectors such as the JA-81M or JA-82M, or
the hard-wired inputs of wireless keypads, or the hard-wired inputs of a
control panel as final-door detectors. This mode is unsuitable for pulse
detectors such as JA-80P motion detectors, or the hard-wired inputs of
JA-81E hard-wired keypads which also have a pulse reaction.
Factory default setting: No final-door detectors in the system.
6.23 Partial setting (arming) or system splitting
The control panel can be configured in three ways as follows:
the entire system sets and unsets together or,
the system partially sets and unsets to protect only certain parts of a
house during the day, while people are still present in the unset parts
or,
the system can be split into two independently set/unset sections for
two separate users and also with a common section if desired.
Program as follows to configure the system as desired:
6 6 x
Where x 0 = unsplit system (setting/unsetting as an entire
system)
1 = partial setting (for setting sections A, AB, or ABC)
2 = split system (sections A and B can be set/unset
independently by separate users, with section C only
being automatically set when both A and B are manually
set)
Notes:
For an unsplit system, all intruder detectors are set/unset
immediately after the user sets/unsets the system. Assigning wireless
devices, access codes and keyfobs to various sections of the system
has no effect in this mode.
Partial setting is especially suitable for homes and apartments where
the user wishes to protect different parts of the premises during the
day. Detectors can be assigned to three sections, A, B and C. Using
setting (arming) key A on the system keypad, you can set section A,
e.g. setting the garage area in the afternoon. Using setting key B you
can set sections A and B simultaneously e.g. in the evening before
going to sleep to protect the garage (section A) and the ground floor of
the house (section B). The ABC total-setting button is used when
leaving the home to set all sections, A,B and C. If you then use a valid
access code or card for unsetting (disarming), all sections will be unset.
The assignment of codes or cards to sections has no effect in this
mode. A and B keypad buttons are used for partial setting.
A keyfob can also be used for partial setting control. Buttons
and
can be programmed to set and unset the entire system, and
buttons + can be programmed for setting (arming) sections A
and AB respectively to partially set the system (this pair of buttons
must be assigned to section A or B if it is to be used for partial setting.
See 6.40 for details on partial setting by keyfob).
Split system mode is especially suitable where two families (A and B)
live in a single house or two companies (A and B) share one building.
The system behaves as two independent systems, one being section A
and the other, section B. There is also a common section C which is
9

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

jablotron-ja-82k-oasis

Suche zurücksetzen

  • Rauchmelder schlägt Alarm ohne Rauch, kann das am Akku liegen? Eingereicht am 29-8-2018 09:05

    Antworten Frage melden
  • Wie kann ich einen irrtümlichen Sabotaschealarm im System neutralisieren?
    Danke Hubert Eingereicht am 21-7-2017 17:57

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Jablotron JA-82K OASIS wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Jablotron JA-82K OASIS

Jablotron JA-82K OASIS Installationsanweisung - Deutsch - 23 seiten

Jablotron JA-82K OASIS Bedienungsanleitung - Englisch - 23 seiten

Jablotron JA-82K OASIS Zusatzinformation - Englisch - 1 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info