Telephone dialer TD-101 / TD-101W - 12 - MDJ512 10 Telephone dialer TD-101 / TD-101W - 13 - MDJ512 10
7.7. Testing the Monitoring Station communication
Communication to the MS can be tested in the installer mode (the yellow LED is ON - see 7.1.), entering:
FM
D
E
where:
D
is the tel. number memory 7 or 8 which will be called
E
means event number (3, 4, 5 or 6) which code will be sent (see item 7.6.)
Example: Report code corresponding to IN2 input triggering (activation) will be sent to the main tel. number :
FM
8. Optional functions and parameters programming
The settings chosen in the Installer mode can significantly customize the dialer operation. This
programming should be done by a professional installer.
8.1. Opening of Installer Mode for Optional functions programming
To enter Installer level from the Standby, enter Installer code IC press
B
and enter Installer
Code IC again. Factory default IC is 1010 so when you open the Installer mode for the first time,
enter
B
. The installer level is indicated by the yellow LED.
All parameters are programmed in the sequences started with
Fkey. If a sequence is entered, the
red LED will start to flash. When the sequence is completely entered, the red LED will turn off (data
will be stored). A started sequence entering can also be terminated by pressing the
Ekey at any
time.
After all programming, the Installer mode must be exited by pressing the
Ekey (all the LEDs will turn
off). The dialer can not be activated in the Installer level !
Note: The installer code IC can also be used to open the user level, the same way as the User Code.
8.2. Dialing method
Pulse or tone dialing can be selected in the Installer mode (the yellow LED is ON - see 8.1.),
entering:
F
D
where:
D
= 0 pulse
D
= 1 tone (factory default)
The dialing method can also be changed from pulse to tone by entering Finside the phone number (it
will insert a pause and it will switch to tone dialing); the
Fkey can not be stored as the first digit.
Example: tone dialing will be selected
F
8.3. Number of voice messages
One or two voice messages can be selected in the installer mode (the yellow LED is ON - see 8.1.),
entering:
F
D
where:
D means number of messages 1 = 1x 20sec. or 2 = 2x 10sec.
(factory default = 2 messages, max. 10sec. each)
If only one message is selected (max. 20sec.) :
• it should be recorded as message no. 1
• IN1 triggering will send the message to
Mem1 and Mem2
• IN2 triggering will send the message to
Mem3 and Mem4
• simultaneous triggering of IN1 and IN2 will send the message to all
Mem1 to Mem4 tel. numbers
• Pager and monitoring station communications will not be effected
• to play the message in stand by press only the
Mkey
Example: Only one voice message, max. 20sec. will be selected :
F
8.4. Trigger inputs IN1 and IN2 logic
The method of IN1 and IN2 triggering can be selected in the installer mode (the yellow LED is ON -
see 8.1.), entering:
F
D
where:
D
= 0 inputs are triggered if the input optocoupler current is switched off (N.C. trigger)
D
= 1 input is triggered if the input optocoupler current is switched on (N.O. trigger)
(factory default setting is 1 = N.O. trigger)
Example: IN1 and IN2 will react to switching the current off (suitable for Normally Closed contacts)
F
8.5. Trigger delay
The dialer reaction delay can be programmed in the Installer mode (the yellow LED is ON - see 8.1.),
entering:
F
D
D can be from 0 to 9, it means that the duration of the delay x10sec (i.e. 0 to 90sec.). Dialing
will start with the delay only if the corresponding Input is triggered longer than the selected
delay. If the input is deactivated before the delay time elapses, the dialer will not work. The delay
is valid for all voice, Pager and Monitoring Station dialing.
Note: triggering with
Fkey or with the remote control (TD-101W) will always have no delay.
(factory default setting is no delay = instant reaction)
Example: Delay 30sec. will be selected :
F
8.6. Number of cycles to send voice & Pager messages
Number of attempts to call each number can be selected in the installer mode (the yellow LED is ON
- see 8.1.), entering:
F
D
D means number of cycles, can be 1, 2 or 3. One cycle means sending of the corresponding
messages to all stored phone numbers in the
Mem1 to Mem6 memories
(factory default setting are 3 cycles)
Example: Two cycles will be selected :
F