636486
39
Zoom out
Zoom in
Vorherige Seite
1/116
Nächste Seite
Engineering information and sizing the heat source
6 720 645 817 (2010/09)
39
5.3 Important hydraulic system components
5.3.1 Hydraulics for maximum utilisation of the
condensing effect
For systems where the heating circuits are connected via
a low loss header, we recommend that the pump is
controlled subject to boiler output. This operating
principle enables the system to operate with maximum
utilisation of the condensing effect.
5.3.2 Underfloor heating system
Due to their low design temperatures, underfloor
heating systems are ideal for combination with a
Suprapur gas condensing boiler. Due to the inertia
during heat-up, we recommend weather-compensated
operation combined with a separate flow
rate-dependent room temperature controller. In
conjunction with the boiler control unit, the FW ...
controllers are suitable for this purpose.
A temperature limiter is required to protect the
underfloor heating system. It should be connected to the
IPM ... For the temperature limiter, contact thermostat
TB 1 can be used, for example.
Automatic system-controlled screed drying is not
possible here, and should therefore be allowed for on
site. Automatic screed drying with the FW ... controller is
only possible via an underfloor heating circuit with
mixer.
5.3.3 Diaphragm expansion vessel
In accordance with DIN EN 12828, water heating
systems must be equipped with a diaphragm expansion
vessel (MAG).
Rough guide to selecting a diaphragm expansion vessel
1. MAG pre-charge pressure
Form. 3 Formula for the MAG pre-charge pressure
(minimum 0.5 bar)
p
0
Pre-charge pressure of the MAG in bar
p
st
Static pressure of the heating system in bar (subject to
building height)
2. System fill pressure
Form. 4 Formula for the system fill pressure
(minimum 1.0 bar)
p
a
System fill pressure in bar
p
0
Pre-charge pressure of the MAG in bar
3. System volume
Subject to various heating system parameters, the
system volume can be checked on the graph in Fig. 25.
4. Maximum permissible system volume
Subject to a maximum flow temperature to be set ϑ
V
and
the pre-charge pressure determined according to
formula 3 p
0
of the MAG, the permissible maximum
system volume for various MAG can be checked in
table 19.
The system volume checked acc. to point 3 in Fig. 25
must be smaller than the maximum permissible system
volume. Select a larger diaphragm expansion vessel if
that is not the case.
Example 1
Given
n System output Q
K
= 200 kW
o Underfloor heating/radiators
Actual
p Total system water content = 4000 l
(Æ Fig. 25, curve a)
Fig. 25 Standard values for average water content of
heating systems
a Underfloor heating system and steel/cast iron radiators
with pipes sized for gravity circulation (20 l/kW)
b Panel radiators (10 l/kW)
c Convectors (6 l/kW)
V
A
Average total water content
Q
K
Rated output
Always use the Suprapur gas condensing
boilers with a low loss header.
p
0
p
st
=
p
a
p
0
0.5 bar+=
.
0
1
2
3
4
5
6
7
8
9
10
11
12
0 100 200 300 400 500 600
a
b
c
V
A
/ m
3
Q
K
/ kW
.
6 720 643 417-29.1O
.
39

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Junkers MKB 400-3 A wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info