The volume of balance tank(8) should be greater than 40L.The drain valve (6) should be installed at the lowest positon
of the system. Pump(10) should be controlled by outdoor unit and connect to corresponding port in the outdoor unit(refer
to 9.7.6 Connection for other components/For outside circulation pump P_o).
NOTE
Pump operation and space heating and cooling
The unit will switch to either heating or cooling mode according to the setting of room thermostat. When space heating/cool-
ing is requested by the room thermostat (5), the pump will start operating and the unit (1) will switch to heating mode/cooling
mode. The unit (1) will operate to achieve the target cold/hot water leaving temperature. In the cooling mode. the motorized
3-way valve (19) will close to prevent cold water running through the floor heating loops (FHL).
The ON/OFF setting of the heating/cooling operation cannot be done on the user interface, the target outlet water temperature
should be set in the user interface.
Domestic water heating
Domestic water heating is as described in 8.2 Application 2.
Make sure to connect the thermostat wires to the correct terminals and to configure the ROOM THERMOSTAT in the
wired controller correctly (see 10.7 Field settings/ROOM THERMOSTAT). Wiring of the room thermostat should follow
method A as described in 9.7.6 connection for other components/For room thermostat.
Wiring of the 3-way valve (19) is different for a NC (normal closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the wiring diagram.
CAUTION
8.4 Application 4
Space heating with an auxiliary boiler (alternating operation).
Space heating application by either the unit or by an auxiliary boiler connected in the system.
The unit controlled contact (also called "permission signal for the auxiliary boiler") is determined by the outdoor temperature
(thermistor located at the outdoor unit). See 10.7 Field settings/OTHER HEATING SOURCE.
Bivalent operation is possible for both space heating operation and domestic water heating operation.
If the auxiliary boiler only provides heat for space heating, the boiler must be integrated in the piping work and in the field
wiring according to the illustration for application a.
If the auxiliary boiler is also providing heat for domestic hot water, the boiler can be integrated in the piping work and in the
field wiring according to the illustration for application b. In this condition, the unit can sent ON/OFF signal to boiler in heating
mode, but the boiler control itself in DHW mode.
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
2
3
Assembly unit Assembly unit
Coding Coding
6
7
8
8.1
8.2
9
10
11
FHL 1…n
12
12.1
12.2
12.3
13
14
15
16
18
4
5
Outdoor unit
Manometer
Pressure relief valve
Expansion vessel
Plate heat exchanger
Air purge valve
Flow switch
P_i: Circulation pump inside the unit
Y-shape filter
Stop valve (field supply)
Wired controller
Drain valve (field supply)
Fill valve (field supply)
Balance tank (field supply)
Air purge valve
Room thermostat (field supply)
19
FCU 1...n
Drain valve
Expansion vessel (field supply)
P_o: Outside circulation pump (field supply)
Collector / distributor (field supply)
Floor heating loop (field supply)
Domestic hot water tank (field supply)
Air purge valve
Heat exchanger coil
Booster heater
T5: DHW tank temp. sensor
Hot water tap (field supply)
P_d: DHW pump (field supply)
One way valve (field supply)
SV1: 3-way valve (field supply)
SV2: 3-way valve (field supply)
Fan coil units (field supply)
17 Bypass valve(field supply)
20
21
Solar energy kit(field supply)
P_s: Solar pump(field supply)
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Kaysun Aquantia PRO Monobloc - KHP-MO wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO Bedienungsanleitung - Deutsch - 88 seiten

Kaysun Aquantia PRO Monobloc - KHP-MO Bedienungsanleitung - Holländisch - 88 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info