5. UNIT INSTALLATION
5.1 Before installation
Before installation
Be sure to confirm the model name and the serial number of the unit.
Handling
Due to relatively large dimensions and heavy weight, the unit should
only be handled using lifting tools with slings. The slings can be fitted
into foreseen sleeves at the base frame that are made specifically
for this purpose.
CAUTION
To avoid injury, do not touch the air
inlet or aluminium fins of the unit.
■ Do not use the grips in the fan
grills to avoid damage.
■ The unit is top heavy! Prevent the
unit from falling due to improper
inclination during handling.
5.2 Selecting the installation site
WARNING
Unit A(mm)
5-16kW ≥2000
Make sure there is enough room to do the installation
Set the outlet side at a right angle to the direction of the wind.
Strong wind
Blown air
Strong wind
Blown air
Be sure to provide for adequate measures in order to
prevent that the unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause
malfunctions, smoke or fire. Please instruct the customer to
keep the area around the unit clean.
1 Select an installation site where the following conditions
are satisfied and one that meets with your customer's approval.
- Places that are well-ventilated.
- Places where the unit does not disturb next-door neighbours.
- Safe places which can bear the unit's weight and vibration
and where the unit can be installed at an even level.
- Places where there is no possibility of flammable gas or product
leak.
- The equipment is not intended for use in a potentially
explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the units' piping and wiring lengths come within
the allowable ranges.
- Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
- Places where rain can be avoided as much as possible.
- Do not install the unit in places often used as a work space.
In case of construction work (e.g. grinding etc.) where a lot of
dust is created, the unit must be covered.
- Do not place any objects or equipment on top of the unit (top
plate)
- Do not climb, sit or stand on top of the unit.
- Be sure that sufficient precautions are taken in case of refrigerant
leakage according to relevant local laws and regulations.
2 When installing the unit in a place exposed to strong wind,
pay special attention to the following.
Strong winds of 5 m/sec or more blowing against the unit's air
outlet causes a short circuit (suction of discharge air), and this
may have the following consequences:
- Deterioration of the operational capacity.
- Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the front of the unit,
the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.
Turn the air outlet side toward the building's wall, fence or screen.
3 Prepare a water drainage channel around the foundation, to drain
waste water from around the unit.
4 If water does not easily drain from the unit, mount the unit on a
foundation of concrete blocks, etc. (the height of the
foundation should be about 100 mm (3.93 in.).
5 If you install the unit on a frame, please install a waterproof plate
(about 100 mm) on the underside of the unit to prevent water from
coming in from the low side.
6 When installing the unit in a place frequently exposed to
snow, pay special attention to elevate the foundation
as high as possible.
7 If you install the unit on a building frame,
please install a waterproof plate (field supply)
(about 100 mm.) on the underside of the
unit in order to avoid drain water dripping.
(See figure).
NOTE
Unit is top heavy!
Try not to install on the building frame.
5.2.1 Selecting a location in cold climates
NOTE
When operating the unit in cold climates, be sure to
follow the instructions described below.
11
12

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Kaysun KEM-07 DVN1 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Kaysun KEM-07 DVN1

Kaysun KEM-07 DVN1 Bedienungsanleitung - Holländisch - 48 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info