A main switch or other means of disconnection, having a contact separation in all poles, must be incorporated in the
fixed wiring in accordance with relevant local laws and regulations. Switch off the power supply before making any
connections. Use only copper wires. Never squeeze bundled cables and make sure they do not come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections. All field wiring and
components must be installed by a licensed electrician and must comply with relevant local laws and regulations.
The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions
given below.
Be sure to use a dedicated power supply. Never use a power supply shared by another appliance.
Be sure to establish a ground. Do not ground the unit to a utility pipe, surge protector, or telephone ground. Incomplete
grounding may cause electrical shock.
Be sure to install a ground fault circuit interrupter (30 mA). Failure to do so may cause electrical shock.
Be sure to install the required fuses or circuit breakers.
This unit is equipped with an inverter. Installing a phase advancing capacitor not only will reduce the power factor
improvement effect, but also may cause abnormal heating of the capacitor due to high-frequency waves. Never install a
phase advancing capacitor as it could lead to an accident.
Fix cables so that cables do not make contact with the pipes (especially on the high pressure side).
Secure the electrical wiring with cable ties as shown in figure so that it does not come in contact with the piping, particularly
on the high-pressure side.
Make sure no external pressure is applied to the terminal connectors.
When installing the ground fault circuit interrupter make sure that it is compatible with the inverter (resistant to high
frequency electrical noise) to avoid unnecessary opening of the ground fault circuit interrupter.
NOTE
The ground fault circuit interrupter must be a high- speed type breaker of 30 mA (<0.1 s).
7.1 Precautions on electrical wiring work
7 FIELD WIRING
WARNING
Equipment must be grounded.
All high-voltage external load, if it is metal or a grounded port, must be grounded.
All external load current is needed less than 0.2A, if the single load current is greater than 0.2A, the load must be controlled
through AC contactor.
7.2 Precautions on wiring of power supply
Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following instructions.
Do not connect different gauge wires to the same power supply terminal. (Loose connections may cause overheating.)
When connecting wires of the same gauge, connect them according to the figure below.
-
-
18
NOTE
Maximum length of communication wirings is 50m.
Power cords and communication wiring must be laid out separately, they can not be placed in the same conduit.
Otherwise, it may lead to electromagnetic interference. Power cords and communication wirings should not come in
contact with the refrigerant pipe so as to prevent the high temperature pipe from damaging the wires.
Communication wirings must use shielded lines.Including indoor unit to outdoor unit PQE line ,indoor unit to controller
ABXYE line.
21

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Kaysun KHPI-BI-16VR2XL wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Kaysun KHPI-BI-16VR2XL

Kaysun KHPI-BI-16VR2XL Bedienungsanleitung - Deutsch - 44 seiten

Kaysun KHPI-BI-16VR2XL Bedienungsanleitung - Holländisch - 44 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info