771572
45
Zoom out
Zoom in
Vorherige Seite
1/84
Nächste Seite
About Running
1 System Structure Figure
Unit has two kinds of heat sources: Heat pump(compressor)
and electric heater.
Unit will automatically select heat sources to heat water to the
target temperature.
2 Water Temperature Display
The temperature shown on the display depends on the upper
sensor. So it is normal that the display temperature has
reached to target temperature but compressor still running,
because the lower water temperature does not get to target
temperature.
Modes will be automatically selected by unit. manually mode
selection is unavailable.
3 Heat source will be automatically selected by unit. But manually
E-Heater operation is available.
4 Heat Source Shift
The default heating source is heat pump.If externalis range out
of heat pump, heat pump will stop running, the unit will shift
automatically to activate E-heater and show the icon LA on
the display, then if the externaltemperature goes into the
running range of heat pump again, it will stop E-heater and
shift automatically to heat pump again, and the icon LA will be
extinguished.
If the target setting water temperature is higher than Max. temp
(Heat pump), the unit will activate heat pump firstly to the Max.
temperature, then stop heat pump, activate E-heater to
continually heat water to the target temperature.
If manually activate the E-heater running mode when heat pump
running, E-heater and heat pump will work together until the
water temperature gets to target temperature.
So if want to heat quickly, please manually activate E-heater.
Note
E-heater will be activated once for the current heating progress,
if want to apply E-heater again please push
E-HEATER.
If system occurs some malfunctions, error code "E7" and , e
will be shown on the display, then heat pump will stop running,
and the unit will activate automatically E-heater as the backup heat
source, but the code "E7" and will be shown until power off.
If only use E-heater, about only 75 liters water (unit 190S) will be
heated or about only 150 liters water (unit 300S), so must set
higher target water temperature if externaltemperature is out of
heat pump running range.
Defrosting During Water-heating
In heat pump running period, if the evaporator frosted in lower
ambient temperature, the system will defrost automatically to keep
effective performance(about 3~10min). At defrosting time, the fan
motor will stop, but compressor will still run.
TCO and ATCO
The power of compressor and E-heater will be automatically shut-
off or turn on by TCO and ATCO.
If the water temperature is higher than 78°C, the ATCO will
automatically shut off the power of compressor and E-heater, and
reconnect it if the temperature falls down below 68°C.
the water temperature is higher than 85°C, the TCO will
automatically shut off the power of compressor and E-heater.
Storage tank
Water outlet
Temperature probe
(T5U)
Electric heater
Water inlet
Temperature probe
(T5L)
9 START-UP
45

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Kaysun Solar Compak KHPA2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info