CO2 CONTROL - assembly and operating instructions
-15-
3.5 Documentation in the dispensing log
The gas detection system must be documented in the dispensing log.
This is done using the "Dispensing log sheet" form which is included in the basic package. The form must be completed together with the operator.
By signing this, the operator confirms the functionality of the gas detection system and their complete understanding of the system.
An additional maintenance plate will also be glued to the dispensing log sheet.
The sensor unit must be exchanged after
four years!
If the exchange date as shown here is
not adhered to, system malfunctions
may occur.
I.
II.
III.
IV.
next exchange!
2020
2021
2022
2023
Recurrent tests and functional checks (of the pre-/main alarm, faults) should also be entered into the dispensing log sheet, together with the date of the test.
For the CO2 CONTROL AM / AM PLUS versions, see the additional notes in the CO2 CONTROL AM / AM PLUS installation sheet.
4 Maintenance / servicing
4.1 General remarks
Safety devices on monitoring equipment must be maintained regularly at the intervals specified by the manufacturer.
The maintenance of the equipment can for example be performed in accordance with BGR 228 by the installation company. The system is maintenance-free
except for the sensor unit. The sensor unit must be replaced by the installer with a replacement unit after 4 years of operation.
4.2 Replacing the CO2 sensor unit
The removal of a sensor unit without connecting a replacement unit is prohibited!
The installer can request replacement units directly from our plant.
A replacement unit must be available before replacing any sensor unit. The seamless operation of the gas detection unit must be ensured.
After swapping the units, pack the old sensor unit in the packaging of the replacement unit and send this back to our plant. After replacing any system
component, the system must be re-initialised!
Important note:
After replacing, the new maintenance plate indicating the replacement date must be applied to the sensor unit, and entered in the dispensing log sheet.
The sensor unit must be exchanged after
four years!
If the exchange date as shown here is
not adhered to, system malfunctions
may occur.
I.
II.
III.
IV.
next exchange!
2020
2021
2022
2023
4.3 Cleaning
Cleaning of the unit is not planned for, nor is this permitted.
4.4 Functional check
A functional check (minimum requirement for the monitoring of detection devices in accordance with BGR 228) of the CO2 CONTROL is not required, and not
necessary due to any maintenance replacement. Where desired, the system can be tested using CO
2
at any time, and the alarm function checked. No test gas is
necessary for this! Since an on-site functional check does not provide sufficient testing of the threshold value tolerances (lack of temperature and pressure
constants), this can only be performed at our plant in accordance with the prescribed test guidelines.
For the CO2 CONTROL AM / AM PLUS versions, see the additional notes in the CO2 CONTROL AM / AM PLUS installation sheet.
15

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Kundo xT CO2 Control wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Kundo xT CO2 Control

Kundo xT CO2 Control Bedienungsanleitung und Installationsanweisung - Deutsch - 54 seiten

Kundo xT CO2 Control Bedienungsanleitung und Installationsanweisung - Deutsch - 53 seiten

Kundo xT CO2 Control Bedienungsanleitung und Installationsanweisung - Holländisch - 52 seiten

Kundo xT CO2 Control Bedienungsanleitung und Installationsanweisung - Französisch - 20 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info