5.4.2 Dynamic 3-101 - 3-118 FU
• Move the door by hand to ist mechanical OPEN travel limit.
• Open housing cover on door operator.
• Release the stop (grub screw J) of control cam (B).
• Set control cam (B) in such way, the the reference point switch (G) is actuated
as shown in fig. 17 (position H), (approx. 2 mm from switch point).
• Fix control cam (B) by screwing on grub screw (J).
• Close the housing cover again.
• Connect to mains and actuate button CLOSE DOOR (12).
The door travels to the travel limit CLOSE, which is pre-set by factory.
Fig. 17: Setting the reference point
English / Page 18
5. Initial Operation of Control Unit Control 144 / 145 / 145 FU
"