1. Parts supplied:
Control 210 automatic timed return in separate housing with two red traffic lights, connecting flange and cable
harness for connection to Control 110 base control unit.
2. Description of operation:
After an impulse has been given with the door closed, both lights flash until the door has reached its final "open"
position. The two lights then go out and the door remains open in accordance with the set "open" time. Once this
time has elapsed, the two lights flash for the duration of the set prewarning phase. Afterwards the door
automatically closes and both lights go out.
3. Setting the "prewarning" and "open" times
The "prewarning" and "open" times are set by means of the rotary switches on the front of the housing.
4. Control sequence:
4.1. An impulse is given by push button, key switch or induction loop etc. The following control sequences are possible:
a) If, with the door closed, an impulse is given to the terminals 43-44 of the Control 210, the door opens.
b) If, with the door open, an impulse is given to terminals 43-44, the opening time is extended, as the timing
for opening is restarted.
c) If, while the door is closing, an impulse is given to terminals 43-44, the door stops for one second, and then
opens again.
If the impulse is given in the Control 110 base control unit (e.g. to terminals 14-15), this cancels out the possibility of
extending the opening time with the door open or of changing the direction while the door is closing.
4.2 Photocell as safety device:
The photocell is connected to terminals 41-42 of the Control 210 automatic timed return (closing function). If the
photocell is interrupted, this activates the control sequences described under 4.1 b) and c). By means of the "S"
switch on the board, the following photocell functions can be set:
"S" ON door stops on interruption of photocell
"S" OFF door stops on interruption of photocell and after one second reopens.
4.3. Switching off the automatic timed return (closing function).
The automatic timed return can be switched off by connecting an ON/OFF switch or by attaching a bridge to
terminals 45-46 of the Control 210 automatic timed return.
5. Connection:
Connect the Control 210 cable harness to the Control 110 base control unit. The S19 programming switch in the
Control 110 base control unit must be in the OFF position. A fuse for safeguarding the electronic equipment and the
red traffic lights is situated on the board of the automatic timed return.
Function of the Control 210 connecting terminals:
L1, N, PE: Mains connection 220 V, 50 Hz
1,2,N: Connection for red traffic lights
V: Motor phase V door drive
12a,13a: "Stop" contact for door controls
13a,36: "Impulse" contact for door controls
5, 37: Limit switch "close"
5, 39: Limit switch "open"
41,42: Photocell connection
43,44: "Impulse" push button, key switch
45,46: Automatic timed return function on/off
Important:
Please observe local safety regulations!
Control voltage 24 V DC
Always lay mains cable and control cable separately!
6. Overview of Control 201 circuit diagram:
F1a Fuse 50 mA
F1b Fuse 4A max.
H40 Green LED "open"
H41,H42 Red traffic lights (entry/exit)
KL Photocell 24 V
K41 "Flashing" relay
K43 "Stop" relay
K44 "Impulse" relay
6

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Marantec Control 210 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info