Mass Systemswitch 16 kW (230V) User and Installation Manual
6.3.3 Menu level 3: Configuration
Value
Meaning
Factory
setting
Adjustable. range
General
Language
Language that is displayed on a monitoring device connected
to the MasterBus
English
English/ Nederlands/
Deutsch/ Français
Device
name
Name of this device. This name will be recognized by all
connected devices
Systemswitch
0-12 chars
Generator
Gen. U low
on
Lower acceptance voltage for pass through of AC power at the
generator input
205V
191-223V
Gen. U low
off
Lower rejection voltage for pass through of AC power at the
generator input
150V
124-177V
Gen. F low
on
Lower acceptance frequency for pass through of AC power at
the generator input
48Hz
41-60Hz
Gen. F low
off
Lower rejection frequency for pass through of AC power at the
generator input
43Hz
35-55Hz
Ignore gen
freq.
If set to On, the generator input ignores the frequency of AC
power at the generator input
Off
Off/On
Generator
Power
Maximum power of the AC-source that is connected to the
Generator input. In general, this is the nominal output power of
the generator set.
16kVA
0-16.0kVA
Names
Shore
name
Name of the AC input Shore
Shore
0-16 characters
Generator
name
Name of the AC input Generator
Generator
0-16 characters
Auto load
on inv.
LOI gen
load
The automatic load on inverter mode (see sections 3.6) will be
triggered when the generator load exceeds this percentage
(percentage of the Generator Power setting).
100%
0-100%
LOI gen
delay
Time delay for the automatic load on inverter mode (see
sections 3.6) caused by a generator overload. It prevents the
automatic load on inverter mode being activated due to a short-
time peakcurrent.
5s
0-30s
LOI
generator
To enable the automatic load on inverter mode triggered by the
generator load, this parameter must be set to “On”
Off
Off/On
LOI shore
load
The automatic load on inverter mode (see sections 3.6) will be
triggered when the shore load exceeds this percentage
(percentage of the Shore fuse setting; see section 6.3.1)
100%
0-100%
LOI shore
To enable the automatic load on inverter mode triggered by the
shore load, this parameter must be set to “On”
Off
Off/On
LOI runtime
When the automatic load on inverter mode is activated, it is
switched off again when the adjusted time has elapsed.
120min
5-540min
Events
Event x
source
Event-based command (see section 5.2)
Event by the Mass Systemswitch that should result in an action
by one of the other devices on the MasterBus network
(See List of events,
section 6.3.4)
Event x
target
Event-based command (see section 5.2)
Selection of device on the MasterBus network that should take
action due to an event. by the Mass Systemswitch
(See Device list on the
remote control panel)
Event x
command
Event-based command (see section 5.2)
Action to be taken by the selected device.
(See List of event
commands in the manual
of the selected device,)
Event x
data
Event-based command (see section 5.2)
Value of the action to be taken by the selected device.
(See List of event
commands in the manual
of the selected device,)
Art. nr
Serial
Shows the article number and the serial number of the Mass
Systemswitch
(read only)
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Mastervolt Mass Systemswitch 16 kW wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info