9
2-INSTALLATION INSTRUCTIONS
Always use pipes and ttings with appropriate seals that guarantee tightness.
It must be possible to inspect all sections of the ue duct and they must be removable for periodic internal cleaning (T-tting with
inspection hole). Position the product considering all the above requirements and instructions.
IMPORTANT!
The following conditions must be complied with when connecting the appliance to the chimney:
• The smoke duct must be at least category T200 (or higher if required by the smoke temperature of the appliance)
and P1-type (airtight).
• All 90° angles (max. 3) in the smoke exhaust duct must be preferably tted with the relative T-ttings with
inspection hole (See pellet product accessories).
• It is strictly forbidden to t a mesh at the end of the exhaust pipe as it could cause the product to malfunction
(due to clogging).
• It is forbidden to use counter-sloping pipes.
• The horizontal section of the smoke duct must not be longer than 2-3 m.
• It is also recommended not to exceed 6 metres in length with the pipe Ø 80 mm.
• The smoke duct must not cross rooms in which it is forbidden to install combustion appliances.
Technical Dept. - All rights reserved - Reproduction is prohibited