PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
page 41
Operation Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
ATTENTION
If the stove is not used as described in this instruction booklet,
the manufacturer refuses to accept any responsibility for
damage to persons and property that may arise. The
manufacturer furthermore refuses to accept responsibility for
damage to persons and property arising from the failure to
observe all the rules contained in the manual and in particular:
• Failure when carrying out works of maintenance,
cleaning and repair to adopt all necessary measures and
precautions
• Tampering with the safety devices.
• Removing the safety devices.
• Failure to connect the stove to an efficient system for the
discharge of smoke.
• Failure to check in advance that the room where the
stove is to be installed is adequately ventilated.
4.17. ALARM SIGNALLING
If there is an operating anomaly, the stove goes into alarm shutdown
mode and informs the user of the type of problem that has occurred via
a 3-figure code displayed on the rear emergency panel.
The alarm is permanently signalled by the corresponding 3-figure code,
by a flashing red light on the emergency panel, and, for the first ten
minutes of the alarm, by a periodic acoustic signal. To take the stove
out of alarm conditions and restore its normal operation, read the
instructions in the next two paragraphs.
The following table summarizes the possible alarms which the stove
may signal and corresponding code which appears on the emergency
panel.
MESSAGE ON
DISPLAY
TYPE OF PROBLEM SOLUTION
A01
Fire fails to ignite
Check the level of pellets in the hopper.
Check that the grate is properly inserted in its housing
and does not have any obvious unburnt incrustations;
Check whether the ignition plug heats.
A02
Fire extinguishes abnormally
he structure is too hot because the product has been
operating for too long at maximum power, or it is
poorly ventilated, or the air fans are faulty. Place
selector D of the rear emergency panel in the OFF
position and wait for the stove to cool. When the stove
is cool enough, the A03 alarm indication on the display
will disappear. Place selector D of the panel in the
REMOTE position to restart the stove using the remote
control.
A04