PELLET STOVES Chapter 2
INSTALLATION AND USE MANUAL
page 12
Theoretical notions for installation Technical service - Rights reserved MCZ GROUP S.p.A. - Reproduction prohibited
2
1
be positioned in such a way as to be impossible to obstruct
It is not compulsory to connect the air intake directly
with the stove (so that it draws air directly from
outside), but it is essential at all events to ensure an
airflow of 50 cubic metres per hour by the use of a
hole of the dimensions given.
See standard UNI 10683.
2.5. CONNECTION OF SMOKE DISCHARGE PIPE
When making the hole for the passage of the smoke discharge pipe, it
is necessary to take into account the possible presence of flammable
materials. If the hole will be going through a wall made of wood or any
other material which is sensitive to heat, the INSTALLER MUST first
of all use the special wall union (diam.13cm 13cm minimum) and
properly insulate the pipe of the stove that passes through it, using
adequate insulation materials (thickness 1.35cm with minimum thermal
conductivity of 0.07 W/m°K).
The same is true if the stove pipe must run through vertical or
horizontal stretches passing in proximity (min.20cm) to the heat-
sensitive wall
As an alternative we recommend the use of insulated pipe, which can
also be used on the outside to avoid condensation.
The combustion chamber works in low pressure. The smoke duct for
the discharge of fumes will also be under low pressure when connected
to an efficient flue pipe as directed.
Pipes and unions with suitable gaskets must always
be used, to guarantee a hermetic seal.
All sections of the smoke duct must be inspectable and
removable to enable periodic internal cleaning. Tee
connectors with inspection caps should be used.
Position the stove bearing in mind all the instructions and
considerations above.
IMPORTANT!
All 90 degree changes of direction in the flue pipe
must be fitted with suitable tee connectors to allow
the possibility of inspection. (see accessories for
pellet stove)
It is absolutely prohibited to fit a grille on the end of
the discharge pipe, because it could lead to poor
running of the stove.
FOR CONNECTION TO THE FLUE PIPE, NOT MORE
THAN 2-3 METRES OF HORIZONTAL PIPE MUST BE
USED AND NOT MORE THAN THREE 90° CURVES
MUST BE USED
IT IS ALSO ADVISABLE NOT TO EXCEED 6 METRES IN
LENGTH WITH THE PIPE Ø 80 mm
Rear view of a pellet stove
1) Combustion air intake
2) Smoke outlet
Example of pellet stove installation