For 3 phase installations, without the need for
hardwiring an external CT, please use the above
diagram.
Earth = Green / Yellow cable
Neutral = Blue cable
Live (L1) = Brown
Live (L2) = Black
Live (L3) = Grey
The recommended torque setting for the electrical
terminals is 1.2Nm
For 3 phase installations, with the need for 1 or more
external/additional CTs, please use the above
diagram.
Positive (+) = Red
Negative (-) = Black
For more details on CT installation and connection
see CT Sensor Installation (Page 36)
has an input which can be used to sense the availability of economy tariff electricity, this can be used to
automatically boost the charge when in ECO or ECO+ charging modes. The eSense input can also be used to limit or
stop the output on an external signal.
The eSENSE input is electrically isolated and effectively draws no current so the cable size is not important. An AC
voltage (between 100V and 260V) across the L and N terminals of the eSENSE input will cause the economy tariff
symbol to be shown on the main screen. The eSENSE Earth terminal is not required to be connected if you do not
want to use this feature or do not have an economy tariff.
See eSense Input on page 34 for details of how to configure the eSENSE input.
Connect the eSense cables using the diagram
Neutral = Blue cable
Live (L1) = Brown cable
There is no need to earth the eSense cable although an earth terminal is available in the
if the cable used has an earth wire.