6 720 815 256 (2014/10) MS 100
30 | Installation
3.3 Electrical connection
Observe current regulations applicable to power
connections, and use at least cable type H05 VV-…
3.3.1 Connecting the BUS connection and temperature
sensor (extra-low voltage side)
If the conductor cross-sections are different, use the
junction box to connect the BUS nodes.
Connect BUS nodes [B] via junction box [A] in star
(Fig. 13, page 197) or via BUS nodes with two BUS
connections in series.
Maximum total length of BUS connections:
100 m at 0.50 mm2 conductor cross-section
300 m at 1.50 mm2 conductor cross-section
All low voltage leads must be routed separately from cables
carrying mains voltage to avoid inductive interference
(minimum separation 100 mm).
In the case of external inductive interferences (e.g. from PV
systems), use shielded cables (e.g. LIYCY) and earth the
shield on one side. The shield should be connected to the
building's earth lead, e.g. to a free earth conductor terminal
or water pipe, and not to the earth lead in the module.
When sensor leads are extended, apply the following lead
cross-sections:
up to 20 m with 0.75 mm2 to 1.50 mm2 conductor cross-
section
20 m up to 100 m with 1.50 mm2 conductor cross-section
Route cables through the grommets provided and connect
them as shown in the connection diagrams.
3.3.2 Connecting the power supply, pump and mixing
valve (mains voltage side)
Only use electrical cable of comparable quality.
Ensure the power supply is connected to the correct
phases.
A power supply via an earthed safety plug is not
permissible.
Only connect components and assemblies to the outputs in
accordance with these instructions. Do not connect any
additional control units, which control other system
components.
Route cables through the grommets, connect them as
shown in the connection diagrams and secure them with
the strain relief pieces, which are supplied as part of the
scope of delivery ( Fig. 9 to 12, starting on page 196
onwards).
3.3.3 Overview of the terminal assignment
This overview indicates which system parts can be connected.
The components identified with * (such as PS5, PS6 and PS9)
of the system are possible alternatives. Depending on the
module's use, one of the components is connected to the
“VS1/PS2/PS3” terminal.
Depending on what the module is used for (coding at the
module and configuration via the user interface), the system
components must be connected as indicated in the relevant
connection diagram (chapter “Connection diagrams with
system schematics”).
More complex solar systems can be created in combination
with a second solar module MS 200. Further terminal
assignments are possible in this case (installation
instructions MS 200).
If the maximum total length of the BUS
connections between all BUS nodes is exceeded,
or if the BUS system is realised as a ring structure,
the system cannot be commissioned.
The allocation of the electrical connections
depends on the system installed. The description
shown in Fig. 9 to Fig. 12, starting on page 196
onwards, is a possible suggestion for making the
electrical connections. Some of the steps are not
shown in black. This makes it easier to see which
steps belong together.
The maximum power consumption of the
connected components and assemblies must not
exceed the output stated in the module
specifications.
If the mains voltage is not supplied via the
electronic system of the heat source, install a
standard all-pole isolator (in accordance with
EN 60335-1) on site to disconnect the mains
voltage.
30

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Nefit MS 100 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info