12 | Commissioning
MZ 1006 720 815 281 (2014/10)
4 Commissioning
4.1 Setting coding switch I
The function of the module is set via coding switch I.
Observe the following:
System with 2-port valve (S-schematic, in UK only): coding switch I to
S
System with mid-position valve (Y-schematic, in UK only): coding
switch I to Y
Example 1: 1 heating zone with 3 unmixed heating circuits:
Module for heating circuits 1, 2 and 3 = coding switch I to 2
or
Module for heating circuits 4, 5 and 6 = coding switch I to 3
Example 2: 1 heating zone with 2 unmixed heating circuits and one
cylinder charging circuit:
Module for heating circuits 1, 2 and cylinder charging circuit =
coding switch I to 1
or
Module for heating circuits 7, 8 and cylinder charging circuit =
coding switch I to 4
The same heating circuit numbers must be set for each of the user
interfaces:
Example 3: system for 4 heating circuits and cylinder charging circuit, 2
MZ 100 modules are therefore required. The coding switches I can be
set to 2 and 4 at these 2 modules. This means heating circuits 1, 2, 3 and
7 are active. In this case, the 4 user interfaces (controllers) of the
heating circuits must also be coded to 1, 2, 3 and 7.
4.2 Setting the temperature switch II
The cylinder setpoint temperature is adjusted via temperature
switch II.
Observe the following:
An installed user interface C 100 instead of the module specifies the
cylinder setpoint temperature via the BUS system. The module will
only specify 15 °C (frost protection) if the cylinder setpoint
temperature is less than 15 °C: temperature switch II to off (2 valid
increment positions).
The module specifies the cylinder setpoint temperature in 5 °C
increments from 40 °C to 70 °C: temperature switch at 40 to 70.
The module specifies 75 °C which is the maximum cylinder setpoint
temperature:
temperature switch to max (2 valid increment positions).
4.3 Commissioning of the module and the system
1. Set the function of the module via coding switch I.
2. If the cylinder setpoint temperature is specified by the module (not
with C 100): set the cylinder temperature via temperature switch II.
-or-
If the cylinder setpoint temperature is specified via a user interface
(with C 100): set temperature switch II to off.
3. If required, set the coding switch and temperature switch at
subsequent modules.
4. Switch on the power supply (mains voltage) to the entire system.
When the module indicator lights up green continuously:
5. Commission and set up the user interface as described in the
accompanying installation instructions.
First make all electrical connections correctly and only then
carry out the commissioning!
Follow all installation instructions for all components
and assemblies in the system.
Make sure that multiple modules do not have the same
coding.
Only switch on the power supply when all modules are
set up.
NOTICE: Connected pumps can start as soon as the
system is switched on unless the control unit has
detected the module.
Fill the system before switching it on so that the
pumps do not run dry.
Number of
heating
circuits
1)
1) Information only applies for user interfaces with EMS 2, for user interfaces with
EMS plus a maximum of 4 heating circuits/zones and 2 cylinders applies
Number of
DHW systems
1)
Coding switch I
Heating circuit
assignments for
user interfaces
(MZ 100 no. 1)
(MZ 100 no. 2)
(MZ 100 no. 3)
1-3 0 2– 1, 2, 3
4-6 0 23 1, 2, 3, 4, 5, 6
7-8 0 234 1, 2, 3, 4, 5, 6, 7, 8
21 1––1, 2
3-5 1 13 1, 2, 4, 5, 6
6-8 1 234 1, 2, 3, 4, 5, 6, 7, 8
1-4 2 14 1, 2, 7, 8
5-7 2 134 1, 2, 4, 5, 6, 7, 8
11 S
2)
2) In UK only
1
11 Y
2)
1
Table 8
WARNING: Risk of scalding!
If DHW temperatures above 60 °C are set or thermal
disinfection is performed (temperature switch II
temporarily above 60 °C), a mixer must be installed.
Temperature switch II
Setpoint temperature of
cylinder
Increment position Inscription
0off10 °C (frost protection)
1–10 °C (frost protection)
24040 °C
3–45 °C
45050 °C
5–55 °C
66060 °C
7–65 °C
87070 °C
9–75 °C
10 Max. 75 °C
Table 9
12

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Nefit MZ 100 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info