Names
Description
Default setting & Other possibility
The following parameters are only visible if a water contact sensor (NTC 10K sensor) is connected and
installed on the incoming pipe of the manifolds, and if the parameter “HC” is on “SenS” position.
(See the schematic and system drawing to install the sensor)
Setting Level to switch your installation between Heat and
cool mode.
When the water temperature (Wtemp) on the incoming pipe
decrease below this setting (minus the hysteresis value/2),
the installation will work in cooling mode.
Wtemp < HCL HCh/2 => System in cooling mode
Wtemp > HCL + HCh /2 => System in heating mode
Press (OK) to view the instantaneous value measured by
the sensor.
Default: 22°C
Adjustable: 5 to 35°C
Hysteresis value for the setting level “HCL”, to avoid quick
commutations between Heat & Cool change.
Default: 5°C
Adjustable: 3 to 10°C
The following parameters are only visible if a water humidity sensor (NTC 10K sensor or free contact
sensor) is connected and installed on the incoming pipe of the manifolds
(See the schematic and system drawing to install the sensor)
Setting level to switch off the cooling function to avoid
residual humidity in the house:
When the water temperature in the pipe decrease under this
level during the time of the anti short cycle adjusted onrHt
the cooling function will be stopped.
Press (OK) to view the instantaneous value measured by
the sensor.
Default: 18°C
Adjustable: 5 to 25°C
Minimum time to decide to stop the cooling function when
the water temperature decreases under the “rHL” level.
Default: 5°C
Adjustable: 3 to 10°C
Delay time (in seconds) for the pump start up after the first
heat demand from minimum one zone.
This function is generally used to avoid noise and damage
of the hydraulic parts of the installation.
Default: 60 s
Adjustable: 0 to 240s
Press (OK) during 5 seconds to reset the installation.
All parameters are replaced by default value.
Press (OK) on this parameter to exit the parameters menu end come back to the main
display.
7. RF ALARM
- You could see the RF alarm on the Master (Red blinking LED on the concerned zone) and on the RF main
zone programmer (in the status line).
- If a RF alarm is detected on one zone, the regulation will be maintained on this zone by average of the actual
room temperatures of the other zones used on the Master.
- Check the thermostat batteries of the concerned zone. If batteries thermostat must be changed, always
replace the 2 batteries in the same time. The RF alarm message should be disappear alone when batteries will
be replaced.
Note:
If all zones are in RF alarm (Red blinking) check the RF antenna connection before replacing of all thermostat
batteries.
7

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Radson 51055 - SLAVE RF wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info