CODE DESCRIPTION
F2 Fuse F 10A
F3 Fuse T 2A
F4 Fuse T 3.15A
FAN (BK, WH, BR) Fan output
FS5 (24V AC) Controller power 24-0-24 Vac
IGN.BOX (L, N) Flame controller power 230 V AC
J1 CAN BUS jumper
J10 Jumper N.O. contact
J82 W10 board connector (on Mod10)
JP10 6-pole flame controller connector
JP12 Fumes sensor or generator fin sensor input
JTAG S61 controller programming connector
MAIN 230V (L, N) S61 controller power 230 V AC
N.O. contact Pump contact, N.O.
P7 (R, W, Y, o) Consent inputs
P8 (GND, L, H) CAN BUS connector
PUMP 230V (L, N) Hydraulic pump power output
SPI Communication port with Mod10 controller
SRT1 Hydraulic pump rotation sensor input
SRT2 Hot water flowmeter input
TA Ambient temperature probe input
TA1 Input probe of evaporator output
TA2 Not used
TCN Combustive air temperature probe input
TF Exhausted gas thermostat input
TG Generator temperature probe input
THMF Hot water delivery temperature probe input
THRF Hot water return temperature probe input
TL Generator limit thermostat input
SCH S61
Figure 5.2 – Mod10 controller
Mod10 controller
LEGEND
HFLOW Not used
CFLOW Condensation water sensor control
J51 SPI connector
HPMP Primary circuit hot water pump control
output (0-10 V) [A/GS/WS]
CPMP Cold side water pump control output
[GS/WS]
NC1-C1 Status indication of locking warnig/error
CN5 Blower control
J82 W10 auxiliary controller connector
J83 W10 cable shielding connection W10
CN1 Inputs 0-10V (not used)
5.1 ELECTRICAL POWER SUPPLY
Use a cable type FG7(O)R 3Gx1.5 for the power supply to the appliance.1.