587905
33
Zoom out
Zoom in
Vorherige Seite
1/44
Nächste Seite
33
For replacing the control board,
several checks must be carried out
and parameters adjusted.
The parameters A1, A2 and
A3 must be adjusted as the
replacement control boards are
supplied neutral.
Every wall gas heater is provided
with a corresponding technical
description with the factory pre-
programmed default values.
This list must be updated with
any locally adapted changes
in order that the replacement
control board can be appropriately
reprogrammed as required.
Checking the control board
hardware confi guration
Check for operation with
temperature control ATR-6:
The jumper NTC/VAN must be on
NTC and the CR switch must be
ON, see diagram below [towards
the inside edge of the board].
This confi guration is necessary to
ensure the correct function of the
NTC sensor.
Jumper on NTC
CR switch
ON
Parameter programming
Programming takes place
exclusively via the temperature
control ATR-6.
The parameters that must be
programmed are:
A1, A2 and A3.
These determine correct
combustion and heat output of the
installed wall heater.
The parameters A1, A2 and A3
are not pre-programmed on
replacement boards.
The values to be adjusted
depending on the particular model
are shown in the table below.
Control board replacement
Model A1 A2 A3
GPM15 44 58 83
GPM25 55 73 83
GPM35 62 93 80
GPM55 65 93 70
GPM75 75 98 70
In order to access the parameters,
press and hold the KM button for
about 10 seconds.
The following appears on the
display:
INFO REG ERR >>
Press the K4 >> button, the
following appears on the display:
SPRA PAR PARK >>
Press the K3 PARK button, the
following appears on the display:
<<
PARAM K 1 >>
The set parameter value 1 appears
above the K4 button and can
be adjusted with the K+ and K-
buttons.
By pressing the K4 >> button,
the parameters from 1 to 3 are
displayed in succession and can
be adjusted with the K+ und K-
buttons.
Chimney sweep button
Set the room temperature (if
necessary) at the temperature
control higher than the actual
room temperature. Wait until the
burner has started.
After switching on the fan, bring
the burner to “maximum output”
by pressing and holding the reset
button on the front of the unit for
2 to 3 seconds.
Operating at maximum output
is indicated by the green LED
ashing rapidly.
After about two minutes, exhaust
gas analysis can be carried out
at the measuring point in the
chimney pipe.
After carrying out the
measurement, set the unit to
“normal” mode by pressing and
holding the reset button again for
2 to 3 seconds.
The green LED fl ashes slowly (min.
output).
Press the reset button again and
the green LED shows a steady light
again.
The normal mode is active again.
Set the room temperature (if it has
changed) to the original value.
d
Z
If the unit is not set to
“normal mode“, the control
board will automatically
reset the unit after 20
minutes.
NOTE
We reserve the right to make changes to dimensions and design in the interest of technological advances.
33

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO GPM 15 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO GPM 15

REMKO GPM 15 Bedienungsanleitung - Deutsch - 44 seiten

REMKO GPM 15 Bedienungsanleitung - Holländisch - 44 seiten

REMKO GPM 15 Bedienungsanleitung - Französisch - 44 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info