Connection of an external
enabling contact (optional)
Operation / standby
In addition to operation with the
controller or cabled remote con-
trol, the unit can be switched on
(standby) and off (normal opera-
tion) using an external floating
contact (programmed as an N.O.
contact) (Fig. 7).
A change in the function logic (as
N.C. contact) is not possible.
This enable is used, for example,
to implement downtimes at night
or an activation/deactivation of a
GLT.
Connection of the collective
fault
message notification function
(standard equipment)
The connection of a floating col-
lective fault message notification
function, for example, for signal-
ling or further processing on a GLT,
is possible in the standard version.
For this purpose, use the corre-
sponding connection diagram and
observe the maximum contact load
(Fig. 7).
7 External floating contacts
2-3 Operation / standby enable (floating)
4-5 External fault message notification function
(max. 230V~, 3A)
2-6 Cooling / heating mode enable (floating)
Unit
Users
Connection of an external
operating mode contact (op-
tional)
for cooling/heating mode
(units with heat pump func-
tion)
In the standard version, the unit
is programmed for operation with
the controller and/or cabled re-
mote control. If a switchover from
cooling or heating mode (Fig. 7)
should take place using an external
floating contact (input), parameter
SP 9 must be reprogrammed to
1 (for the programming, see the
"Configuration of the switchover
between cooling and heating"
section). After the switchover, only
the external enable for cooling/
heating mode can be used.
Configuration of the switchover between cooling and heating
(external contact)
The controller is programmed at the factory for the switchover between
cooling and heating on the controller. When an external contact is used
to switchover between cooling and heating, a regulation parameter must
be reconfigured. Parameter SP 9 must be switched over from 0 to 1. In
the SP menu item, the parameter SP 9 can be changed in level 1.
Factory setting for KWP...H heating:
Switchover between cooling and heating Parameter SP 9 = 0
"0" = operation on controller, "1" = operation through switchover con-
tact
The following program sequence must be programmed.
After the programming procedure, the "heating
mode" is activated with an open contact between
terminals 2 and 6. Display =
After the programming procedure, the "cool-
ing" is activated with a closed contact between
terminals 2 and 6. Display =
Configuration of parameter SP 9
+
> 5 sec.
< 2 sec.
< 2 sec.
< 2 sec.
> 5 sec.
< 2 sec. ...
< 2 sec. ...
+
> 5 sec.
Normal
display
St
submenu
Entry
C-H switchover
Parameter
C-H switchover
Input
Parameter level
Standby
mode
Open parameter
SP 9
SP
submenu
Entry
assumed
/
> 5 sec.
REMKO KWG
32
32

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO KWG1300 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO KWG1300

REMKO KWG1300 Bedienungsanleitung - Deutsch - 60 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info