587983
19
Zoom out
Zoom in
Vorherige Seite
1/60
Nächste Seite
Malfunction
Fault Code Possible cause Check Remedy
The unit
does not
start or
switches
itself off
autono-
mously
Power failure
Is all other electrical equipment
functioning?
Check the voltage and wait for
reactivation.
Unit fuse / main disconnecter
switched off
Does the unit have power?
Switch on the unit fuse / main
switch.
Waiting period too short Is the compr. symbol flashing?
Plan for a longer waiting
period.
C(n)Mn
The maintenance interval
of compressor (n) has been
reached
Have the compressor mainte-
nance performed by a specialist
company
Reset the operating hours after
the maintenance interval.
AEP(n)
The maintenance interval of
the circulation pump has been
reached
Have the circulation pump
maintenance performed by a
specialist company
Reset the operating hours after
the maintenance interval.
APS /
ASPh
Incorrect electrical direction of
rotation of the mains supply
Has the phase sequence relay
switched through?
Change the direction of rota-
tion.
StbY
The controller is in standby
mode
Does the compressor symbol
light up?
Apply voltage and
select the operating mode.
Return temperature or param-
eter setting incorrect
Check the setting. Change the settings.
OFF No fault
Is the "external enable" ena-
bling contact closed?
Close / open
contact used.
AP1 Defective sensor, medium inlet Check of resistor PB1 Replace the defective sensor.
AP2
Defective sensor, medium
outlet
Check of resistor PB2 Replace the defective sensor.
AP 3-6 Defective transm. condensation Check of transmitter PB Replace the defective transmit..
AP
Defective sensor, outdoor tem-
perature
Check of resistor PB Replace the defective sensor.
Atr1
Cabled remote control not con-
nected
Check of the connection / line
of the cabled remote control
If missing, set Parameter CF 74
from "1" to "0"
b(n)HP
High-pressure fault
Circuit n
Are the fans rotating?
Is the air inlet of the condenser
free of objects?
Have it checked by
a specialist company.
b(n)LP
Low-pressure fault
Circuit n
Is the pressure in the cooling
circuit OK?
Have it checked by
a specialist company.
b(n)hP Overtemperature of condenser
Are the fans rotating?
Is the air inlet of the condenser
free of objects?
Have it checked by
a specialist company.
b(n)hP
Undertemperature of condenser
Circuit n
Have the operating tempera-
tures been exceeded?
Decommission the system.
b(n)AC
b(n)AH
Anti-frost protection has
reacted
Circuit n
Is the temperature of the inlet
flow 4°C or lower?
Increase the return temperature,
increase the medium volume
flow rate
.
AEFL
Differential pressure monitor /
flow monitor
reacted
Are the following items OK:
- Medium volume flow rate
- No air in the medium
lines
- Circulation pump capacity
- Switches the differential pres-
sure /
flow monitor
- Shut-off valves open
- Medium pressure too low
Have it checked by
a specialist company.
Atr1
Cabled remote control not
configured or connected
Does the cabled remote control
function perfectly?
Have the remote control and/
or parameters checked by a
specialist company.
AEt1,
b(n)tF,
A(n)tr,
b(n)HP
APS /
ASPh
Control fuse F1 230V triggered Has fuse F1 triggered?
Have the fuse replaced by a
specialist company.
19
19

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO KWG750 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO KWG750

REMKO KWG750 Bedienungsanleitung - Deutsch - 60 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info