REMKO KWG
54
Series
KWG
400
SP
KWG
500
SP
KWG
600
SP
KWG
750
SP
KWG
850
SP
KWG
950
SP
KWG
1100
SP
KWG
1300
SP
KWG
1500
SP
KWG
1750
SP
Function
Air-cooled compact chiller with multi-stage power control and
circulation pump / storage tank for cooling
Nominal cooling capacity
1)
kW 39.5 49.7 58.4 75.9 84.5 93.3 112.6 129.4 151.8 173.5
Energy efficiency ratio for cooling
EER
8)
2.32 2.42 2.45 2.48 2.37 2.42 2.58 2.48 2.53 2.48
Return temperature operating range
Cooling
°C +10 to +18
Operating range, cooling °C +15 to +45
Operating range, cooling (expansion) °C +5 to +45
5)
/ -15 to +45
6)
Number of cooling circuits 1 2
Power gradation % 0/50/100
0/33/
66/100
0/31/
62/100
0/33/
66/100
0/22/50/
72/100
0/25/50/
75/100
0/17/33/50/
67/83/100
Refrigerant R 410A
7)
Max. refrigerant operating pressure kPa 4200
Refrigerant, basic amount per cooling
circuit
kg 9.8 12.0 11.2 12.9 13.7 14.1 20.5 2x12.9 2x12.1 2x17.1
Compressor, number/type 2/scroll 3/scroll 4/scroll 6/scroll
Number of condenser fans 1 2 3
Max. air volume flow rate m³/h 21800 21200 21200 44400 44400 44400 43400 42400 66000 62580
Sound pressure level
3)
dB(A) 50.7 50.7 51.0 53.9 54.0 54.3 54.3 54.3 55.7 55.8
Sound power level dB(A) 82.9 82.9 83.2 86.1 86.2 86.5 86.5 86.5 87.9 88.0
Voltage supply V/Hz 400/3~/50
Type of protection IP 24
Max. electrical power consumption
4)
kW 26.04 29.23 34.91 47.06 53.64 58.07 66.94 78.49 90.27 103.93
Max. electrical current consumption
4)
A 38.14 42.74 50.95 68.59 78.10 84.50 97.31 114.16 131.18 151.55
Electrical nominal power consumption,
cooling
1)
kW 17.01 20.51 23.81 30.59 35.59 38.49 43.70 52.23 59.94 70.04
Electrical nominal current consump-
tion, cooling
1)
A 26.30 31.63 36.65 47.01 54.62 59.04 66.95 80.06 91.78 107.74
Max. electrical starting current LRA A 112.80 131.10 142.20 172.50 166.40 166.40 201.20 188.70 231.80 235.20
Operating medium Max. 35% ethylene glycol; max. 35% propylene glycol
Operating limits of medium °C +4 to +18
Max. medium operating pressure kPa 600
Nominal volume flow rate, medium
cooling
m³/h 6.80 8.53 10.04 13.07 14.54 16.06 19.37 22.25 26.10 29.84
Minimum flow rate, medium m³/h 5.40 6.80 8.00 10.40 11.60 12.80 15.40 17.80 20.80 23.80
Maximum volume flow rate, medium m³/h 8.10 10.20 12.00 15.60 17.40 19.20 23.20 26.70 31.30 35.80
Max. nominal pump pressure kPa 166.0 160.0 154.0 149.0 143.0 138.0 124.0 151.0 128.0 141.0
Nominal pressure loss, internal cooling kPa 21.6 26.8 25.7 25.4 18.7 22.8 22.9 31.3 35.8 34.4
System pressure, available cooling kPa 144.4 133.2 128.3 123.6 124.3 115.2 101.1 119.7 102.2 106.6
Diaphragm expansion vessel, volume l 5.0 5.0 5.0 10.0 10.0 10.0 10.0 10.0 18.0 18.0
Diaphragm expansion vessel, pre-
pressure
kPa 150
Medium port, inlet Inch 1 1/2 1 1/2 1 1/2 2 2 2 2 2 1/2 2 1/2 2 1/2
Medium port, outlet Inch 1 1/2 1 1/2 1 1/2 2 2 2 2 2 1/2 2 1/2 2 1/2
Medium contents, pipelines l 5.6 5.8 6.0 8.4 8.6 8.9 9.4 9.6 15.6 15.9
Tank volume l 150.0 150.0 150.0 300.0 300.0 300.0 300.0 300.0 300.0 300.0
Dimensions - height mm 1954 1954 1954 1954 1954 1954 1954 1954 1954 1954
Width mm 1123 1123 1123 1123 1123 1123 1123 1123 1123 1123
Depth mm 1955 1955 1955 3005 3005 3005 3005 3005 4255 4255
Weight kg 613.1 638.6 644.4 817.2 894.0 896.7 952.1 1061.6 1196.4 1401.9
Approx. operating weight kg 828.9 855.0 861.4 1208.4 1285.8 1289.4 1350.3 1460.4 1625.2 1831.6
Serial colour similar to RAL 9018
Serial number RAL 9018
1033...20.. 1033...21.. 1033...22.. 1033...23.. 1033...24.. 1033...25.. 1033...26.. 1033...27.. 1033...28.. 1033...29..
Reference number RAL 9018
1690410 1690510 1690610 1690760 1690860 1690960 1691110 1691310 1691510 1691760
1) Air inlet temperature TK 35°C, medium inlet 12°C, medium outlet 7°C, 0% glycol concentration
2) Air inlet temperature TK 7°C, medium inlet 45°C, medium outlet 50°C, 0% glycol concentration
3) Distance 10 m in open air
4) Air inlet temperature TK 45°C, medium inlet 18°C, medium outlet 15°C, 0% glycol concentration
5) Only with the compressor crankcase heating as accessory
6) Only with the winter fan control set as accessory
7) Contains greenhouse gas according to Kyoto Agreement
8) Determined according to EN 14511
54

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO KWG750 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO KWG750

REMKO KWG750 Bedienungsanleitung - Deutsch - 60 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info