Diaphragm expansion vessel
To prevent pressure fluctuations
during standstills due to
temperature changes, diaphragm
expansion vessels with a nitrogen
filling (moisture-neutral) must be
integrated into the system.
The standard version of the
KWG...P, KWG...SP, KWP...P,
and KWP...SP units include a
diaphragm expansion vessel. The
volume of these diaphragm expan-
sion vessels are designed only for
those units. The system requires an
additional diaphragm expansion
vessel designed for this system.
An individual design is required for
the KWG and KWP units.
The calculation can be performed
with roughly 5 to 10% diaphragm
expansion vessel volume of the
system volume.
The pre-pressure of all diaphragm
expansion vessels must be set on
the system.
Safety valve 6.0 bar
Safety valves limit an operating
pressure that is too high due to ex-
cessive heating or an overfilling of
the operating medium. The valve
outlet requires a free feed into a
drain line. When glycol is used, the
local disposal regulations must be
observed.
The standard version of the unit
includes a safety valve.
Bleeding valves
The unit has manual bleeding
valves. After the filling of the
system, the unit can be bled here
separately. In addition, automatic
bleeding valves must be mounted
at the highest point of the collec-
tive line.
When media containing glycol
are used, glycol-resistant
bleeding valves must be used.
ATTENTION
Capacitors
In order not to transmit the
vibrations of the chiller to the
system parts, we recommend the
use of capacitors to connect the
lines to the unit, in addition to
Victaulic connectors.
Capacitors
Shut-off valve Capacitor
Static
fastening
KWG connection
Shut-off valves
In cold water systems, shut-off
valves with full throughput should
fundamentally be used. For
servicing purposes, the medium
inlet and medium outlet must be
equipped with shut-off valves
(with safety valve, if required).
Circulation pump for KWG and
KWG...SP
For units without a storage tank,
an external circulation pump is
required for the implementation
of the nominal volume flow rate
within the chiller!
Actuation takes place via the ter-
minal strip using a controller of the
chiller.
Incorrectly installed or missing
dirt traps can cause a soiling of
the plate heat exchanger.
ATTENTION
Filling and bleeding connection
A connection for bleeding the
pipelines (especially when water
is used as the medium) should be
provided in the anti-frost-protect-
ed area. When glycol is used, the
local disposal regulations must be
observed.
Dirt trap
A rinsable dirt trap must be in-
stalled in front of the unit inlet.
The mesh size should not exceed
10 meshes/cm². Shut-off valves
should be used upstream and
downstream of the dirt trap.
If the minimum medium volume
flow rate of the system is under-
shot, malfunctions may result.
NOTE
Anti-frost protection (accessory)
A water/glycol mixture is usu-
ally used as the medium of a cold
water system. According to the
glycol type and amount used, the
viscosity changes, the pressure
loss increases, and the dissipated
cooling and/or heating capacity
of the unit decreases. All system
components must be released for
use with glycol.
In general, we recommend that
34% ethylene glycol with in-
hibitors for corrosion protection be
added to the water. This concen-
tration guarantees anti-frost safety
up to –20°C; at lower tempera-
tures, an ice slush that no longer
has a bursting effect arises.
If the medium could come into
contact with drinking water or
food, a toxicologically harmless
medium based on propylene glycol
must be preferred.
REMKO KWG
28
28

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO KWG950 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO KWG950

REMKO KWG950 Bedienungsanleitung - Deutsch - 60 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info