2-conductor system for cooling and heating
As the 2-conductor system must cool and heat
equally, for reasons of convection during winter
operation, a valve assembly is stipulated for all
installation methods for this system operation to
avoid undesirable heat emission.
4-conductor system for cooling and heating
As the 4-conductor system must cool and heat
equally, two valve assemblies are stipulated for this
system operation for the cooling and heating reg-
ister.
Connection of the medium pipings
nThe connection of the lines on-site takes place
on the rear or underside of the unit.
nFor the purpose of servicing, connections must
be equipped with shut-off valves and the
medium flow rate adjusted using valves for
hydronic balancing.
nAdditional automatic bleed valves are to be
provided in the supply and return flow at the
installation’s highest point.
nThe medium pipings may not exert any struc-
tural load on the unit.
nThe line connections may not generate any
thermal or mechanical stresses on the unit. If
necessary, cool the piping or support with the
second tool.
Necessary system components
Valve assembly for 2 or 4-conductor systems
(accessory)
In 2 or 4-conductor systems, cold or warm medium
is fed through the heat exchanger(s) into the unit
and cold or warm air can be discharged. Regula-
tion is provided by a 3-way valve assembly. It con-
sists of the electrically actuated valve head and the
valve body. If the head is electrically activated, it
actuates the body, which routes the medium into
the register. If the temperature is reached, the
head is switched off and the medium is fed past
the heat exchanger through the bypass. The
bypass serves to ensure the minimum medium
flow rate for the chiller.
The time between being fully open and fully
closed can be approx. three minutes.
Valves for hydronic balancing
The calculated individual pressure losses in the
pipeline network layout for each individual unit are
adjusted to the entire system with hydronic bal-
ancing valves to be provided by the customer. The
nominal flow rates for the medium adjust to the
values needed as a consequence of the pressure
loss.
Anti-freeze protection (accessories)
A water glycol mix is generally used as the medium
for a cold water system. Depending on the glycol
type and quantity used, the viscosity changes, the
pressure loss increases and the unit's cooling or
heating capacity reduces.
All system components must be approved for use
with glycol.
NOTICE!
The product and safety data sheets of the
glycol type used must be observed during use
and disposal.
Diaphragm expansion vessel (MAG)
To avoid pressure fluctuations during standstill
because of temperature changes, diaphragm
expansion vessels filled with nitrogen (moisture
neutral) must be integrated in the system.
No moisture can condense in the nitrogen filler.
Safety valve
Safety valves limit excess operating pressure due
to excess warming or overfilling of the operating
medium. The valve outlet requires unobstructed
draining into a drain line. Applicable local disposal
ordinances must be observed if glycol is used.
Automatic bleed valves
The unit has one or two manual bleed valves on
the collector pipe of the register. The unit can be
bled separately after the system has been filled.
Automatic bleed valves must also be installed at
the next highest point in the collective lines.
23
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO KWK ZW serie wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO KWK ZW serie

REMKO KWK ZW serie Bedienungsanleitung - Deutsch - 40 seiten

REMKO KWK ZW serie Bedienungsanleitung - Holländisch - 40 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info