Electrical connection
For devices of series MVT 600-
1050 DC, an electrical supply
must be laid as mains supply to
the outdoor unit as well as the
supplied 4-core control line from
the indoor unit to the outdoor
unit.
We recommend that screened
control lines are used with
a minimum cross-section of
1.5 mm².
Connecting the outdoor unit
Before making the connection,
observe the following information:
Customers should install
a terminal box in the vicinity of
the outdoor unit.
We recommend that a main/
repair switch is used (Figure 9).
Voltage is supplied to the
indoor unit through the
connection cable between
the outdoor component and
outdoor unit.
Details concerning the electrical
protection of the system are
given in the technical data.
Observe the required
diameters!
If the outdoor unit is installed
on a roof, ensure it is protected
against lightning strikes.
Label the electrical control lines
and the associated refrigerant
pipes of each interior device
with the same letter (A to D).
9 Connecting the outdoor unit
A vacuum of min. 20 mbar
must be created!
CAUTION
The time required to generate
the vacuum is dependent on
the pipework volume of the
indoor unit and the length of the
refrigerant pipes. This always takes
at least 60 minutes.
Once any foreign gases and
humidity have been completely
extracted from the system, the
valves on the pressure gauge
station are closed and the valves
on the outdoor unit are opened
as described in the chapter on
"Commissioning".
All electrical installation
work should be performed
by specialist contractors.
Isolate the voltage supply
when connecting the electrical
terminals.
CAUTION
10 Connecting the cable
Strain relief
Plug control
line indoor
unit A
Plug control
line indoor
unit C
Plug control
line indoor
unit B
Terminal block
Mains cable
Only connect the lines to their
associated connections as
labelled with the same letter.
Mixing up the assignment
of control lines and
refrigeration pipes can lead
to fatal consequences such as
compressor damage!
Proceed as follows to connect the
cable:
1. Remove the side panel next to
the terminals.
2. Select the cable cross-section
according to the relevant
standards.
3. Feed the cables through the
edge protection rings on the
fixed connection panel.
4. Insert the control lines into
the corresponding sockets. In
doing so, pay attention to the
alignment of the circuits.
5. If the supplied control lines
are too short, they can be
unclamped from the indoor unit
and extended by an electrician.
6. Support the cable in the strain
relief and re-assemble the unit.
Check all plugged and clamped
terminals to verify they are
seated correctly and making
a permanent contact. Re-tight-
en as required.
CAUTION
Additional sensor and control
lines may be required on some
indoor units.
NOTE
REMKO MVT
16
16

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO MVT600 DC wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO MVT600 DC

REMKO MVT600 DC Bedienungsanleitung - Deutsch - 24 seiten

REMKO MVT600 DC Bedienungsanleitung - Deutsch - 28 seiten

REMKO MVT600 DC Bedienungsanleitung - Holländisch - 28 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info