587735
12
Zoom out
Zoom in
Vorherige Seite
1/28
Nächste Seite
12
Troubleshooting
This unit has been designed using state-of-the-art manufacturing processes and it has been tested repeatedly to
ensure that it is working properly. However, should problems occur, refer to the following list.
If all functional checks have been performed and the unit is still not operating properly, contact the closest dealer or get in
touch directly with REMKO GmbH & Co. KG.
G G
The power cord must be disconnected from the power source (fuse and repair switch) and
secured against being accidentally switched on before any work is done on the unit!
Problem Possible cause Check Remedy
The device does not start or
switches itself off automatically.
Power failure, low current, electri-
cal supplier network problems
Are all other electrical components
working? Is the green LED on the
indoor unit blinking? Was the power
supply interrupted temporarily?
After power returns:
RKS 327 to 371: starts again in the
selected mode after 3 minutes.
Defective power fuse / main switch
is off
Are all currents for lighting
functional?
Replace power fuse /
Switch on main switch
Power supply line damaged Are all other electrical components
working?
Maintenance by authorised service
centre
Amount of time waited after switch-
ing the unit on was too short
Did approximately five minutes
elapse after starting the device?
Schedule longer waiting periods
Temperature during operation is
either too high or too low
Are the fans on the indoor unit and
the outdoor part working ?
Pay attention to the temperature
ranges of the indoor unit and the
outdoor part
Excess current from thunderstorms Was there recently lightning in the
area?
Switch off the power fuse and re-
start / maintenance by authorised
personnel
Problem with the external conden-
sation pump
Did the pump switch trigger an
automatic shut-down ?
Check pump and clean if neces-
sary
Board, fuse or sensors have inter-
nal defect
LEDs for Operation, Pre.Def. or
Timer blinking 5 times per second?
Maintenance by authorised service
center
The indoor unit does not respond
to the remote control.
Timer setting to “On” Is the timer set? Delete programming and wait for
the unit to start
New batteries have been incor-
rectly inserted
Are the ends lined up properly? Insert batteries correctly
Transmission distance is too far /
reception disrupted
Transmission signal when the but-
ton is pressed at a distance of ap-
prox . 3 m ?
Reduce distance to less than 6 m
and change location
Remote control is defective Does the unit operate in manual
mode?
Replace remote control
The sun is too strong on the re-
ceiver or transmitter
Does the unit work in the shade? Cover the transmitter or receiver
Electromagnetic fields are disrupt-
ing transmission
Does the unit function after elimi-
nating possible sources of disrup-
tion?
No signal transmission when de-
vices which are potentially disrup-
tive are operated simultaneously
Remote control button is stuck / two
buttons being pressed simultane-
ously
Does this symbol appear on the
display?
Unstick button / only press one
button
Remote-controlled batteries are
dead
Have new batteries been inserted?
Is the display incomplete?
Replace batteries
Temperature setting too high Is the selected temperature higher
than the temperature of the room?
Lower selected temperature
Dirty filter / input or output opening
blocked by foreign objects
Have the filters been cleaned? Clean filters
Windows and doors open / In-
creased need for heating / cooling
capacity
Has there been a change in the
design or use of the unit?
Close windows and doors / assem-
ble additional units
“Cool” function not set Is the cooling symbol ( )
activated on the display?
Correct the unit setting
“Heat” function not set Is the heating symbol ( )
activated on the display?
Correct the unit setting
Plate fins of the outdoor part
blocked by foreign objects
When the fan of the outdoor part is
running, can the exchanger plate
fins move freely?
Check fan or winter regulation
mechanism, reduce air resistance
Condensation is leaking from the
indoor unit.
Drainage hose of the collection
container is blocked / damaged
Can condensation drain freely from
the unit?
Clean drainage hose and collec-
tion container
External condensation pump or
float regulator defective
Is the collection container full of wa-
ter and the pump is not working?
Have pump replaced by authorised
service centre
The unit is either not cooling/
heating at all or only a little bit.
COOL
HEAT
12

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO RKS371H wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO RKS371H

REMKO RKS371H Bedienungsanleitung - Deutsch - 26 seiten

REMKO RKS371H Bedienungsanleitung - Holländisch - 28 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info