Minimum distances
The chart below indicates the minimum distances that
must be maintained to ensure that the units operate
properly.
A B C D E
RKS 327 H AT 200 900 300 100 200
RKS 335 H AT 200 900 300 100 200
RKS 350 H AT 200 1200 300 150 400
RKS 371 H AT 300 1500 300 150 600
A
B
E
C
D
Assembly Instructions for
Service Personnel
Important instructions prior to installation
àOnly use the swivel nuts supplied with the refrigerant
lines. Other components can damage the thread.
àThe units are only suitable for limited use in com-
puter rooms because after a power outage there is
no guarantee that the units will restart. It is also pos-
sible that they will only start again with specific set-
tings.
àThe unit-specific, maximum length of the refrigerant
line is 10 or 15 m respectively with a maximum
height difference of 5 or 8 m.
àEnsure the contents of the package are complete
and that the unit has no visible damage from trans-
port.
àAny problems must be communicated directly to
your contract partner and the shipping company.
Subsequent complaints will not be acknowledged.
àPlace the units in their original packaging as close as
possible to the location where they will be set up to
prevent damage from transport.
àDo not install the outdoor part and the indoor unit in
the direct vicinity of objects that emit intense heat.
Reflective glass surfaces, lights, etc.
àThe condensation line must be placed at an incline
of at least 2 % .
àIf this line is connected to the drainage line, an odour
seal must be installed the upper edge of which may
not extend beyond the lower edge of the indoor unit.
àPrior to installation, the electrical values must be
checked for consistency with the data on the type
plate.
àRemove the protective caps of the unit connections
just before connecting the refrigerant lines.
àAll electrical connections must meet the relevant re-
quirements.
àThe power supply is only connected to the indoor
unit. The unit-specific connection and sensor lines
leading to the outdoor part should be placed together
with the refrigerant lines.
àThe indoor unit and the outdoor part of the REMKO
air-conditioner are adjusted to one another from a
technical standpoint.
The guarantee becomes null and void if third-party
components are used .
àRemember that when installing and maintaining air
conditioners, high-pressure and electrical current
can pose hazards.
àDuring unit operation, some components in the cold
cycle can reach temperatures of more than 70 °C.
Be especially careful when covers are removed.
àThe air intake and outlet openings may not be
blocked by furniture, curtains, etc.
àThe refrigerant lines may not be bent or pressed.
àProtect open refrigerant lines from moisture with
caps or tape.
àPrevent unnecessary bends to minimise the pres-
sure loss in the refrigerant lines and ensure that the
compressor oil can recirculate properly.
àIf the outdoor part is mounted above the indoor unit,
make sure to take steps to recirculate the oil (oil ele-
vation arcs).
àSelect a location to set up the unit where air can flow
freely in and out of the device. Minimum distances
can be found in chart below
àMake sure that the electrical lines have been prop-
erly attached in the electrical terminals.
àMake sure that all refrigerant lines including all con-
nectors and valves are insulated against heat and
sealed against diffusion.
Wall lead-throughs
Wall lead-throughs are necessary to establish the con-
nection between the indoor unit and the outdoor unit.
Please observe the following:
àFor the connection line to the outdoor part, a lead-
through of at least 70 mm in diameter must be cre-
ated.
àThe lead-through must be placed at an incline of at
least 10 mm between the inside and outside.
àBefore beginning work, make sure that there are no
supply lines (water, etc.) located in the vicinity of the
wall lead-through.
àWe recommend cushioning the inside of the hole or
lining it with a PVC pipe to prevent the lines from be-
ing damaged.
àAfter assembly is complete, the wall lead-through
must be sealed with a suitable sealing compound.
Do not use any materials containing cement or lime!
15

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO RKS371H wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO RKS371H

REMKO RKS371H Bedienungsanleitung - Deutsch - 26 seiten

REMKO RKS371H Bedienungsanleitung - Holländisch - 28 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info