6.4 Adding refrigerant
The units contain a basic quantity of refrigerant. In
addition, an additional amount of refrigerant must
be added for refrigerant piping lengths exceeding 5
metres per circuit. Refer to the following chart:
Up to and
incl. 5m
From 5m to
max. length
RVD 355 DC
0 g/m
15 g/m
RVD 525 DC
RVD 685 DC
30 g/m
RVD 1055 DC
CAUTION!
W
ear protective clothing when handling refrig-
erant.
DANGER!
Only refrigerant in a liquid state may be used to
fill the cooling cycle!
NOTICE!
Check the overheating to determine the refrig-
erant fill quantity
.
NOTICE!
The escape of refrigerant contributes to climatic
change. In the event of escape, refrigerant with
a low greenhouse potential has a lesser impact
on global warming than those with a high
greenhouse potential.
This unit contains refrigerant
with a greenhouse
potential of 675. That means the escape of 1 kg
of this refrigerant has an effect on global
warming that is 675 times greater than 1 kg
CO
2
, based on 100 years. Do not conduct any
work on the refrigerant circuit or dismantle the
unit - always enlist the help of qualified experts.
7 Condensate drainage
connection and safe
drainage
Condensate drainage connection
If the temperature falls below the dew point, con-
densate will form on the cooling fins during cooling
mode. A collection tray together with a condensate
pump and liquid level switch are fitted as standard
below the cooling fins. If the liquid level switch trips
a protective shutdown due to inadequate removal
of the condensate, the pump will switch on immedi-
ately and run on for approx. three minutes.
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer
. If necessary, fit vapour-diffusion-
proof insulation.
n If the level of the condensate drainage line on
the unit is above that of the outlet, route the
pipe vertically upwards and then with an incline
to the drain.
n Route the unit's condensate drainage line
freely into the drain line. If the condensate runs
directly into a sewer pipe, fit a trap to prevent
any unpleasant odours.
n When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate
drainage line is laid to protect it against frost. If
necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
Safe drainage in the event of leakages
Local regulations or environmental laws, for
example the German W
ater Resource Act (WHG),
can require suitable precautions to protect against
uncontrolled drainage in case of leakage to provide
for safe disposal of escaping air conditioning fluid
or hazardous media.
NOTICE!
The max. pump pressure of the condensate
pump is 500/750 mmWS. Capacity reductions
can result from external influences such as air-
side counter-pressure, soiling or wear. In order
to guarantee safe functional operation, we rec-
ommend observing a maximum delivery height
of 450/700 mm!
31
31

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO RVD 355 DC wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO RVD 355 DC

REMKO RVD 355 DC Bedienungsanleitung - Deutsch - 84 seiten

REMKO RVD 355 DC Bedienungsanleitung - Holländisch - 84 seiten

REMKO RVD 355 DC Bedienungsanleitung - Französisch - 84 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info