Anti-freeze protection (accessories)
As a medium for a cold water
system, a water-glycol mixture
is used as a rule. Depending on
the use to which the glycol type
and quantity is put, the viscosity
changes, the loss in pressure
increases and the unit's cooling
or heating capacity reduces.
All system components must be
approved for use with glycol.
As a rule, the addition to the
water of ethylene glycol, in a
proportion of 34%, with inhibitors
for corrosion protection is
recommended.
Diaphragm expansion vessel (MAG)
To avoid pressure fluctuations
during standstill because of
temperature changes, diaphragm
expansion vessels filled with
nitrogen (moisture neutral) must
be integrated in the system.
Safety valve
Safety valves limit excess operating
pressure due to excess warming
or overfilling of the operating
medium. The valve outlet requires
unobstructed draining into a drain
line. Applicable local disposal
ordinances must be observed
if glycol is used.
The standard scope of delivery
for the unit includes a safety
valve; an additional valve may
be necessary at a suitable point.
Compensators
Compensators are used to connect
lines to the unit to prevent vibration
in the chiller from transmitting
to other system components.
Compensators
Shut-off valve Compensator
Static fasten-
ing
Unit connection
Air bleeding valves
The unit has manual air bleeding
valves. The unit can be bled here
after the system has been filled.
Automatic bleeding valves must
also be installed at the highest
point in the collector line.
Dirt trap
A rinsable dirt trap must be
installed upstream from the unit
intake. The mesh size should not
be less than 10 mesh/cm². Shut-
off valves should be installed
upstream and downstream from
the dirt trap.
External medium storage tank
If, for example, the required
capacity of the cold water
consumer is significantly less
than the cooling capacity
generated by the chiller, an
increase in the medium content
is recommended. As an example,
the medium piping can be
oversized or an additional
storage tank installed to increase
compressor operating time.
A storage tank should, as a rule,
be provided if the minimum
medium volume is not reached.
Shut-off valves
As a rule, in cold water systems,
shut-off valves with full admission
should be used. For the purpose
of servicing, medium inlet and
medium outlet must be equipped
with shut-off valves (if necessary
safety valves).
Glycol-tolerant air bleeding
valves are necessary when
using media that contain
glycol.
CAUTION
!
Improperly installed or missing
dirt traps can cause fouling
of the plate heat exchanger.
CAUTION
!
During use and
disposal, product and safety
data sheets for the glycol
type being used as well
as applicable local ordinances
(e.g. Water Resources Act)
must be observed.
CAUTION
!
Use the required type and
mix ratio appropriate for
the application area to ensure
the freezing point.
CAUTION
!
23
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO RVS DC serie 50-80-130-180 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO RVS DC serie 50-80-130-180

REMKO RVS DC serie 50-80-130-180 Bedienungsanleitung - Deutsch - 44 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info