726585
28
Zoom out
Zoom in
Vorherige Seite
1/84
Nächste Seite
6.3 Connection of
refrigerant piping
The refrigerant piping is connected on the back
side of the units.
It may be necessary to fit a reducer or flared
adapter to the indoor unit. These fittings are
included with the indoor unit as an accessory kit.
Once installed, the connections should be insu-
lated to make them vapour dif
fusion proof.
NOTICE!
Installation should only be performed by author-
ised specialists.
NOTICE!
The unit is factory filled with dry nitrogen for
leak testing purposes. The pressurised nitrogen
is released when the union nuts are undone.
NOTICE!
Use only tools which are approved for use in an
HVAC environment. (z. B.: bending pliers, pipe/
tubing cutters, de-burrers and flaring tools). Do
not cut refrigerant pipes with a saw.
NOTICE!
All work must be carried out in a way that pre-
vents dirt, particles, water etc. from entering,
refrigerant lines!
The following instructions describe the installation
of the cooling cycle and the assembly of the indoor
unit and the outdoor unit.
1. The required pipe diameters are given in the
table "T
echnical data".
2. Install the indoor unit and connect the refrig-
erant piping as described in the operating
manual for the indoor unit.
3. Use the wall or floor brackets to fit the out-
door unit against structural parts approved to
support the static load (refer to the installa-
tion instructions for the brackets).
4. Ensure that structure-borne sound is not
transferred to parts of the building. Use vibra-
tion dampers to reduce the ef
fects of struc-
ture-borne sound!
5. Lay the refrigerant piping from the indoor unit
to the outdoor unit. Ensure that the fasten-
ings are adequate and if necessary
, take
appropriate oil return measures!
6. Remove the factory-fitted protective caps and
union nuts on the connections. These should
be used later in the installation process.
7. Before flanging the refrigerant piping, ensure
that the union nut is fitted on the pipe.
8. Prepare the laid refrigerant piping as shown
below (
Fig. 31 and Fig. 32).
9. V
erify that the shape of the flange is correct
(Fig. 33).
10. First connect and hand-tighten the refrigerant
piping to ensure it is correctly seated.
11. Then tighten the fittings with 2 appropriately-
sized open-ended spanners. Use one
spanner to counter the force when tightening
the fitting (Fig. 34).
12. Use insulation hoses which are designed for
this temperature range and are dif
fusion
proof.
13. Observe the permitted bending radius for the
refrigerant piping during installation. Never
bend a pipe twice in the same place. Brittle-
ness and cracking can result.
14. Apply appropriate heat insulation to the
installed refrigerant piping, including con-
nector
.
15. T
ake the same action at the shut-off valves
for all subsequent refrigerant piping.
REMKO RXT series
28
28

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO RXT 525 DC wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO RXT 525 DC

REMKO RXT 525 DC Bedienungsanleitung - Deutsch - 84 seiten

REMKO RXT 525 DC Bedienungsanleitung - Holländisch - 84 seiten

REMKO RXT 525 DC Bedienungsanleitung - Französisch - 84 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info