Technical data
Series RXT 351DC RXT 521DC RXT 681DC RXT 1051DC RXT 1401DC
Operating mode Inverter wall-mounted room air conditioner combination for cooling and heating
Nominal cooling output
1)
kW
3,51 (1,41-4,02) 5,27 (1,63-5,65) 7,03 (1,63-7,92) 10,55 (3,01-13,22) 14,01 (3,41-15,62)
Nominal heating output
2)
kW
4,02 (1,42-4,75) 5,86 (1,45-6,15) 7,76 (1,75-8,61) 11,72 (3,75-14,02) 15,47 (4,23-16,50)
Energy efficiency rating, cooling
1)
A A A A A
Energy efficiency rating EER
1)
3,55 3,34 3,22 3,25 3,24
Energy efficiency rating, heating
2)
A A A A A
Coefficient of performance COP
2)
3,76 3,86 3,66 3,87 3,62
Power consumption, yearly,
(500h) C / H
495 / 535 790 / 760 1090 / 1060 1625 / 1515 2165/2135
Usage area
(room volume), approx.
110 160 230 320 470
Refrigerant R 410A
4)
Power supply V/Hz 230 / 1~ / 50 400 / 3~ / 50
Rated electr. power
consumption, cooling
1)
kW
0,99 (0,32-1,27) 1,58 (0,44-2,32) 2,18 (0,84-2,35) 3,25 (2,31-5,02) 4,33 (2,51-5,95)
Rated electr. power
consumption, heating
2)
kW
1,07 (0,36-1,38) 1,52 (0,36-2,44) 2,12 (0,72-2,72) 3,03 (2,03-5,91) 4,27 (1,45-5,51)
Max. rated electr. power
consumption
kW
2,55 2,40 3,25 5,00 5,50
Rated electr. current
consumption, cooling
1)
A
4,67 (1,68-5,90) 7,09 (1,95-10,50) 10,30 (3,65-11,52)
4,72 (3,80-7,53) 6,27 (3,80-8,83)
Rated electr. power
consumption, heating
2)
A
5,05 (1,89-6,41) 6,81 (1,65-11,60) 10,05 (3,22-12,81) 4,47 (3,49-8,98)
6,19 (2,18-8,48)
Electr. starting current, max. A 12 14 15,5 7,5 7,8
Refrigerant connection,
injection line
Inches
(mm)
1/4 (6,35) 1/4 (6,35) 3/8 (9,52) 3/8 (9,52) 3/8 (9,52)
Refrigerant connection,
suction line
Inches
(mm)
1/2 (12,70) 1/2 (12,70) 5/8 (15,90) 5/8 (15,90) 5/8 (15,90)
Max. operating pressure kPa
4200 / 2500
Data specific to indoor unit
RXT 351DC IT RXT 521DC IT RXT 681DC IT
RXT 1051 DC IT
RXT 1401DC IT
Setting range for room temperature
°C +17 to +30
Operating range °C +17 to +32
Air flow volume per speed setting
m³/h 460/520/580 500/600/800 960/1080/1150
1000/1200/1400
1600/1800/2000
Sound pressure level per speed setting
3)
dB(A) 33/37/40 38/41/43 40/43/46 42/44/47 44/46/47
Protection class IP X0
Condensation connection mm 25
Dimensions - Height mm 660 660 660 660 680
Width mm 990 990 990 1280 1670
Depth mm 206 206 206 206 245
Weight kg
18,0 29,0 29,0 37 52
Data specific to outdoor
component
RXT 351DC AT RXT 521DC AT RXT 681DC AT
RXT 1051DC AT
RXT 1401DC AT
Operating range, cooling °C +5 to +43
Operating range, heating °C -15 to +24
Air flow rate, max. m³/h 1600/2500 2300/2570 3000/3250 4800/5000 5800/6000
Protection class IP 24
Sound pressure level, max.
3)
dB(A) 48 51 53 55 58
Refrigerant, basic quantity kg 1,40 1,60 2,30 2,9 3,6
Refrigerant, additional quantity > 5 m
g/m 30 30 30 30 30
Refrigerant pipe, max. length
m 15 25 25 30 50
Refrigerant pipe, max. height m 10 10 10 20 20
Flow regulator Capillary tube Electronic Electronic Electronic Electronic
Dimensions - Height mm 590 675 835 940 1235
Width mm 760 845 895 990 940
Depth mm 270 325 335 335 335
Weight kg 39,0 59,0 73,0 87,0 99,0
Serial number 1034... 1035... 1036... 1037... 1038...
EDP no. 1619430 1619440 1619450 1619460 1619470
1) Air intake temperature TK 27°C / FK 19°C, outdoor temperature TK 35 °C, FK 24 °C, max. air flow volume, 5m pipe length
2) Air intake temperature TK 20°C, outdoor temperature TK 7°C, FK 6°C, max. air flow volume, 5m pipe length
3) Gap 1 m free space 4) Contains greenhouse gas according to Kyoto Protocol
REMKO RXT...DC
52
52

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für REMKO RXT681 DC wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von REMKO RXT681 DC

REMKO RXT681 DC Bedienungsanleitung - Deutsch - 52 seiten

REMKO RXT681 DC Bedienungsanleitung - Französisch - 56 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info