Doc890/3456CV02B 47
Setting the fl ow temperature for Domestic Hot Water (cover open)
N.B. Only applicable if the Direct Hot Water function is used with the BM-E expansion module.
- Open the lid
- Turn the rotational switch (pos.5) clockwise until the arrow at the bottom of the LCD display
indicates parameter P2
- Press the combined Reset/Programming key (pos. 3). The LED will light. Turn the rotary switch
(pos.5) until the desired water fl ow temperature has been reached
- Press the combined Reset/Programming key. The LED will go out
- Close the cover.
N.B. The new temperature setting will only become active once the Reset/Programming key has
been released.
6.4 Fault indications
A fault always results in a fl ashing E symbol and a fault code appearing in the display. When a
fault occurs, the cause must always be found and corrected before the related protective function
is reset. If a fault occurs 3 times or more within half an hour, the fault code will be appearing in the
display with an additionally “3” above it. The boiler can be nevertheless in operation.
1 The high limit thermostat has operated. The boiler tempera ture has exceeded 100°C. Press
the reset button.
2/3 The interlocking input has been interrupted. Correct the external error and press reset.
4/5 Ionisation fault. Press reset.
6 Temperature protection has operated. The boiler tempera ture has exceeded the setting.
Press reset.
7 The lockout input has been interrupted. Correct the external fault and press reset.
11 Error in fl ame signal. A fl ame has been detected during start-up. Correct the fault and press
reset.
12 Flow temperature sensor is faulty. Correct fault.
13 Wiring of the CXE/EM extension module is defective. Cor rect fault.
14 Hot water temperature sensor is defective. Correct fault.
15 External temperature sensor is defective.Correct fault.
18 Header temperature sensor is defective. Correct fault.
20 Error in the control of gas valve 1. After burner has stopped a ame has been detected for a
period of 5 seconds. This in spite of the fact that valve 1 is closed. Correct the fault by clean-
ing the valve.
21 Error in the control of gas valve 2. After burner has stopped a ame has been detected for a
period of 5 seconds. This in spite of the fact that valve 2 is closed. Correct the fault by clean-
ing the valve.
22 A i r ow too low. The air pressure switch has not operated. Press reset.
23 The air pressure switch has not switched off. Press reset.
27 The air pressure switch switched off during operation.
30 CRC error in EEprom data group “Boiler. Press reset.
31 CRC error in EEprom data group “Burner. Press reset.
32 Fault in 24 V circuit. Correct fault.
40 Error detected in the position of the fl ow switch. The fl ow switch is tested under two condi-
tions:
- No heat demand - pump stop - fl ow switch must return in rest position.
- Heat demand - pump turns - fl ow switch detects water fl ow.
Not adhering to the above conditions will give the error condition. Correct fault.
X.Y. An internal fault has been detected during the self-test. Press reset.
44

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Rendamax R3500 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info