SATEL PERFECTA LTE 27
partitions is armed. If the option is disabled, the zone is armed when both partitions are
armed.
Active in Day Arm [364.Day active] – if the option is enabled, the zone is armed when the
day armed mode is activated.
Active in Night Arm [363. Night act.] – if the option is enabled, the zone is armed when the
night armed mode is activated.
Entry delay [34.Entry delay] – the time by which alarm from the zone of 0. E
NTRY
/E
XIT
or
1. E
NTRY
/E
XIT FINAL
type will be delayed. It is counted from the moment of zone violation.
During the countdown, the zones of 2. I
NTERNAL
type act as delayed ones. You can enter
from 0 to 255 seconds. Programming 0 will make the zone act as an instant one.
Delay [34.Entry delay] – the time by which alarm from the zone of 2. I
NTERNAL
type will be
delayed. It is counted from the moment of zone violation. You can enter from 0 to 255
seconds. Programming 0 means that the zone will act as an instant one.
Waiting time [34.Entry delay] – the time during which the 4. D
OUBLE KNOCK
type zone has to
be violated again for the alarm to be triggered. It is counted from the first violation of the
zone. You can enter from 0 to 255 seconds. Programming 0 means that the W
AITING TIME
is 30 seconds.
Delay activation time [34.Entry delay] – the time during which the 2. I
NTERNAL
type zones
act as delayed ones. It is counted from the moment of violation of the 18. E
NTRY
R
OUTE
E
NABLING
type zone. You can enter from 0 to 255 seconds.
Arming mode [39.Arm mode] – the armed mode activated by violating the zones of
13. A
RM
/D
ISARM
or 14. A
RM
type. You can select full, day or night armed mode.
Trouble code [35.Trouble code] – violating of the 19. T
ROUBLE
type zone can generate event
that will be reported.
Priority [366.Priority] if the option is enabled, starting the arming procedure is impossible
when the zone is violated. If the option is enabled for a zone of the 0. E
NTRY
/E
XIT
,
1. E
NTRY
/E
XIT FINAL
or 2. I
NTERNAL
type and the zone is violated at the moment the
partition exit delay countdown expires and the partition is armed, a warning alarm will be
triggered. If the partition is not armed after exit delay countdown expires, the warning
alarm will not be triggered.
Auto-reset 3 [367.3 alarms] – if the option is enabled, the zone can trigger up to 3 alarms. As
long as the alarm is not cleared or the partition is not armed/disarmed, violations of the
zone will not trigger any alarm.
Bypass disabled [368.Bps disable] – if the option is enabled, the user cannot bypass the
zone.
Alarm clearing [372.Alarm clear] – an option for the 13. A
RM
/D
ISARM
and 15. D
ISARM
zone
types. If the option is enabled, together with disarming, the alarm is cleared. Violation of
the 15. D
ISARM
type zone will also clear the alarm, when the system is not armed.
Zone restore disarms [369.Shnt.disarm] – an option for the 17. S
HUNT LOCK
zone type. If
the option is enabled, the zone restore will disarm the partition.
Store zone violations events [370.Viol.event] – an option for the 12. N
O ALARM ACTION
zone
type. If the option is enabled, the zone violation is saved to the event log.
Store zone restore events [371.Rest.event] – an option for the 12. N
O ALARM ACTION
zone
type. If the option is enabled, the zone restore is saved to the event log.
6.2 Zone types
0. E
NTRY
/E
XIT
– when the E
XIT DELAY
countdown is in progress, zone violation will trigger no
alarm. When the partition is armed, zone violation will start the E
NTRY DELAY
countdown.
The user have to disarm the partition before the E
NTRY DELAY
expires, otherwise, the alarm
29

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Satel PERFECTA 32 LTE wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Satel PERFECTA 32 LTE

Satel PERFECTA 32 LTE Bedienungsanleitung - Deutsch - 11 seiten

Satel PERFECTA 32 LTE Zusatzinformation - Deutsch - 50 seiten

Satel PERFECTA 32 LTE Installationsanweisung - Deutsch - 27 seiten

Satel PERFECTA 32 LTE Kurzanleitung - Englisch - 10 seiten

Satel PERFECTA 32 LTE Bedienungsanleitung - Englisch - 30 seiten

Satel PERFECTA 32 LTE Zusatzinformation - Englisch - 50 seiten

Satel PERFECTA 32 LTE Installationsanweisung - Englisch - 26 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info