EN
Leak detection methods
The following leak detection methods are deemed acc eptable for all
refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in
the case of ammable refrigerants, the sensitivity may not be adequate ,
or may need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensur e that the detector is not a potential source of
ignition and is suitable for the refrigerant used . Leak detection equipment
shall be set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant emplo yed, and the appropriate percen tage of
gas (25 % maximum) is conrmed.
Leak detection uids are suitable for use with most refrigeran ts but the
use of detergents containing chlorine shall be av oided as the chlorine may
react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked ames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recov ered from the system, or isolated (by means of
shut o valves) in a part of the system remote from the leak. F or appliances
containing ammable refrigerants, o xygen free nitrogen (OFN) shall then
be purged through the system both bef ore and during the brazing process
Removal and evacua tion
When breaking into the refrigerant circuit to make r epairs – or for any other
purpose – conventional proc edures shall be used. However , for ammable
refrigerants it is important that best practice is followed since ammability
is a consideration. The following procedur e shall be adhered to:
• remove refrigeran t;
• purge the circuit with inert gas;
• evacuate;
• purge again with inert gas;
• open the circuit by cutting or brazing.
The refrigerant charge shall be rec overed into the correct reco very
cylinders. For appliances containing ammable r efrigerants, the system
shall be “ushed” with OFN to render the unit safe. This process may need
to be repeated several times . Compressed air or oxygen shall not be used
for purging refrigeran t systems.
For appliances c ontaining ammable refrigerants, ushing shall be
achieved by breaking the vacuum in the system with OFN and continuing
to ll until the working pressure is achieved, then v enting to atmosphere,
and nally pulling down to a vacuum.
This process shall be repeat ed until no refrigerant is within the system.
When the nal OFN charge is used, the system shall be v ented down
to atmospheric pressure to enable w ork to take place. This operation is
absolutely vital if brazing operations on the pipe-work are to take place.
Ensure that the outlet of the vacuum pump is not close to any ig nition
sources and that ventilation is a vailable.
Charging procedur es
In addition to conventional charg ing procedures, the follo wing
requirements shall be follo wed.
• Ensure that contamination of dier ent refrigerants does not occur when
using charging equipment. Hoses or lines shall be as short as possible to
minimise the amount of refrigerant contained in them.
• Cylinders shall be kept upright.
• Ensure that the refrigeration system is earthed prior to charging the
system with refrigerant.
• Label the system when charging is complete (if not alr eady).
• Extreme care shall be taken not to overll the operefrigeration system.
Prior to recharg ing the system, it shall be pressure-tested with the
appropriate purging gas.
The system shall be leak-tested on c ompletion of charging but prior to
commissioning. A follow up leak t est shall be carried out prior to leaving
the site.
Decommissioning
Before carrying out this procedure, it is essential that the t echnician
is completely familiar with the equipment and all its detail. It is
recommended good practice that all refrigerants ar e recovered safely .
Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to reuse of r eclaimed refrigerant. It is
essential that electrical power is available befor e the task is commenced.
a. Become familiar with the equipment and its operation.
b. Isolate system electrically.
c. Before attempting the proc edure, ensure that:
mechanical handling equipment is available, if required, for handling
refrigerant cylinders;
all personal protective equipment is available and being used
correctly;
the recovery process is supervised at all times by a competent
person;
recovery equipment and c ylinders conform to the appropriat e
standards.
d. Pump down refrigerant syst em, if possible.
e. If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f. Make sure that cylinder is situated on the scales before reco very takes
place.
g. Star t the recov ery machine and operate in accordance with
manufacturer's instructions.
h. Do not overll cylinders. (No more than 80 % volume liquid charge).
i. Do not exceed the maximum working pressure of the cylinder , even
temporarily .
j. When the cylinders have been lled correctly and the process
completed, make sure that the cylinders and the equipment are
removed from sit e promptly and all isolation valves on the equipment
are closed o .
k. Recovered refrigerant shall not be charged in to another refrigeration
system unless it has been cleaned and checked.
Labelling
Equipment shall be labelled stating that it has been decommissioned and
emptied of refrigerant. The label shall be dated and signed. F or appliances
containing ammable refrigerants, ensur e that there are labels on the
equipment stating the equipment contains ammable refrigerant.
Recov ery
When removing refrigerant fr om a system, either for servicing or
decommissioning, it is recommended good pr actice that all refrigerants
are removed saf ely.
When transferring refrigerant into cylinders, ensur e that only appropriate
refrigerant recov ery c ylinders are employed. Ensur e that the correct
number of cylinders for holding the total system charge are av ailable.
All cylinders to be used are designated for the rec overed refrigerant
and labelled for that refrigerant (i.e . special cylinders for the recovery of
refrigerant). Cylinders shall be complet e with pressure-relief valve and
associated shut-o valves in good working order . Empty recovery cylinders
are evacuated and, if possible , cooled before recov ery occurs.
The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recov ery of all appropriate refrigerants including, when applicable,
ammable refrigerants. In addition, a set of calibrated weighing scales
shall be available and in good working order . Hoses shall be complete
with leak-free disconnect couplings and in good condition. Befor e using
the recovery machine, check that it is in satisfactory working order , has
been properly maintained and that any associated electrical components
are sealed to prevent ig nition in the event of a refrigerant release. C onsult
manufacturer if in doubt.
The recover ed refrigerant shall be returned to the refrigerant supplier
in the correct recovery cylinder , and the relevant waste transfer note
arranged. Do not mix refrigerants in reco very units and especially not in
cylinders.
If compressors or compressor oils are to be r emoved, ensure that they hav e
been evacuated to an acceptable lev el to make certain that ammable
refrigerant does not remain within the lubricant. The evacuation proc ess