INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
34
-
the course of the day. This function is active primarily during the transition periods such as spring
or autumn. It prevents the immediate reactions of the system to the outside temperature
fluctuation.
The HC1 limit comfort parameter defines the modified outside temperature (see chap. 5.8.1.) that
represents the limit for granting the permission to heat in the mode Comfort.
The parameter setting is ranging from 5 – 30°C; the default value is 18°C.
The instructions for changing this parameter can be found in chapter 4.
The HC1 limit reduce parameter defines the modified outside temperature (see chap. 5.8.1.) that
represents the limit for granting the permission to heat in the mode Reduce.
The parameter setting is ranging from 2 – 30°C; the default value is 17°C.
The instructions for changing this parameter can be found in chapter 4.
C) Summer/winter switch
If the user does not want the system to automatically switch to the summer mode according to the
development of the outside temperature, s/he can define the “summer” and “winter” modes
manually.
6.4.4. ROOM PARAMETERS HC1
After clicking on the line Room parameters HC1 it is possible to enter the menu where all
parameters related to the internal temperatures of the room HC1 can be set, which are monitored
by the room temperature sensor (e.g. room unit A6 - SIEMENS POL 822.70).
The Frost protection HC1 parameter defines the internal temperature at which the reference
room HC1 is heated at the time when according to the TSP HC1 the mode “frost protection” is
active.
The parameter setting is ranging from 4 – 19°C; the default value is 10°C.
The instructions for changing this parameter can be found in chapter 4.
The Reduce HC1 parameter defines the internal temperature at which the reference room HC1 is
heated at the time when according to the TSP HC1 the mode “reduce” is active.
The parameter setting is ranging from 10 – 21°C; the default value is 19°C.
The instructions for changing this parameter can be found in chapter 4.
The Comfort HC1 parameter defines the internal temperature at which the reference room HC1 is
heated at the time when according to the TSP HC1 the mode “comfort” is active.
The parameter setting is ranging from 19 – 35°C; the default value is 21°C.
The instructions for changing this parameter can be found in chapter 4.
The Room influence parameter defines the influence of the room HC1 temperature (expressed as
a percentage) at the expense of the outside temperature B9 on reaching the required temperature
for heating and for heating shutdown in the reference room HC1.
Room influence Control mode
0 % Only weather-compensated control.
1 – 99 % Weather-compensated control and room influence.
100 % Only room control, the outside temperature B9 is not taken
into account.
34

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens Climatix 2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info