WARNING!!! After the functionality check, it is necessary to switch all the aggregates to the mode
Auto again. The indicators on buttons "A" and "B" - see chap. 2 - stop blinking.
7.4. BOILER PUMP
The line Boiler pump is used to set all the parameters that are necessary for correct operation of
the pump of the primary circuit.
The parameter Switch ON temperature determines the temperature at which the pump of the
primary circuit is turned on if this pump is controlled by the control equipment of the boiler.
The parameter setting is ranging from 40 – 60 °C; the default value is 45 °C.
The instructions for changing this parameter can be found in chapter 4.
When water in the boiler is cooling, the pump of the primary circuit is turned off according to the
hysteresis set in the Differential OFF parameter and after expiry of a period set in the Pump
overrun time parameter.
The setting of the parameter Differential OFF is ranging from 1 to 10 °C; the default value is 5 °C.
The instructions for changing this parameter can be found in chapter 4.
The setting of the parameter Pump overrun time is ranging from 0 – 30 min; the default value is 2
min.
The instructions for changing this parameter can be found in chapter 4.
Example:
The values set in the control equipment are:
- Switch ON temperature 45 °C
- Differential OFF 5 °C
- Pump overrun time 2 min
If the boiler is put into operation, the temperature of water in the boiler starts to rise. If it
reaches the value of 45 °C, the pump of the primary circuit turns on. If the temperature of
water in the boiler starts to fall, for any reason, and if it reaches the value of 40 °C (45-5=40)
and this value does not change for 2 min, the pump turns off.
After passing the time set in the Pump overrun time parameter, the pump also turns off if the
boiler switches to the mode “External reduce” - see chap. 6.2. - or if the room thermostat of the
external input disconnects. If they connect again, the pump automatically turns on.
If the temperature of water in the boiler rises above 85 °C, the boiler pump is in continuous
operation, regardless of the operating mode of the boiler. It turns off if the temperature falls below
85 °C and the overrun time is 2 min.
The selection Frost protection (OFF/ON) defines whether pump of the primary circuit is in the
mode “frost protection” or not. If ON is selected, the pump of the primary circuit is turned on
according to the actual value of the outside temperature B9, even if no demand on heating is
received.
52

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens Climatix 2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info