INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
55
-
simultaneously. When the boiler switches to the mode “Reduce” or when the boiler turns off, the
flue gas outlet turns off after its overrun time.
The default value is Ignition. The instructions for changing this parameter can be found in chapter
4.
The Overrun time of flue gas outlet parameter determines the delay time of putting the flue gas
outlet out of operation compared to the ignition aggregate (or the combustion air fan).
The parameter setting is ranging from 0 – 300 sec; the default value is 20 sec.
The instructions for changing this parameter can be found in chapter 4.
7.7. PARAMETERS FOR BACKFIRE
In order to minimize the risk of backfire of the fuel in the storage tank, the control equipment
communicates with the backfire sensor which is installed in the feeding mechanism. If this sensor
monitors the unacceptable increase in the feeder temperature (c. 100°C), the transport of fuel into
the burner accelerates (as defined by the parameters Feeding time and Delay time described in
this chapter) for the time that is defined by the parameter Protection time. After this time passes,
during the Intervention period, the backfire control is not taken into consideration (this period is
intended for cooling the feeding mechanism) and the boiler operates in the normal mode.
The Feeding time parameter determines how long the screw feeder is in operation during
activation of the backfire sensor.
The parameter setting is ranging from 2 – 10 s; the default value is 5 s.
The instructions for changing this parameter can be found in chapter 4.
The Delay time parameter determines how long the screw feeder is out of operation during
activation of the backfire sensor.
The parameter setting is ranging from 5 – 60 s; the default value is 20 s.
The instructions for changing this parameter can be found in chapter 4.
The Protection time parameter determines how long the accelerated fuel feeding is active after
activation of the backfire sensor.
The parameter setting is ranging from 1 – 30 min; the default value is 5 min.
The instructions for changing this parameter can be found in chapter 4.
The Intervention period parameter determines how long it takes before the activation of the
backfire sensor is re-evaluated. Then, the transport of fuel into the burner can be accelerated
again.
The parameter setting is ranging from 10 – 120 min; the default value is 60 min.
The instructions for changing this parameter can be found in chapter 4.
7.8. SUBSTITUTE OPERATION
This function is activated only if the function Cascade in the Configuration (chap. 7.1.) is turned
off.
The selection Including boiler OFF - YES enables to control the appliances even if the boiler is
turned off. It is assumed that a substitute unit is available.
55

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens Climatix 2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info