INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
59
-
Simulation outside temperature - if the function “Simulation outside temperature” is used
during putting the boiler into operation or during resetting the modified or attenuated
temperature and setting the new required value, the control equipment indicates that this
function is being used for the service technician not to forget to turn off this function after
finishing the process. If stars are set on the respective line, the function turns off.
Safety thermostat - indicates that the boiler is overheated and its temperature exceeds the
temperature set by the used safety thermostat – see chap. 9.2.
O2 Heater error - if the oxygen sensor is used, this message indicates that heating of the
monitoring part of the sensor does not work. It may be caused by the incorrect connection,
by the loss of supply voltage or by the sensor damage, e.g. by silicone vapors in flue gases.
Boiler hopper lid - indicates either the boiler hopper lid is opened (if the boiler hopper lid
sensor is used) or that the thermocontact of the boiler feeder is overheated.
Loss of flame - operation - it indicates that the fuel in the burner has burnt out (loss of
flame) when the configuration of the boiler without ignition is used. It may be caused by the
operator failure to refill the fuel storage tank, crust formation of caked fuel, by the incorrect
setting of the fuel feeding during operation, etc. The limit for activating this error can be set
in the service menu and it is necessary to find an optimal setting when the boiler is put into
operation according to the type and quality of the fuel and according to the structure of the
heating system.
Loss of flame - reduce - it indicates that the fuel in the burner has burnt out (loss of flame)
when the configuration of the boiler without ignition or without emptying is used. It may be
caused by the operator failure to refill the fuel storage tank, crust formation of caked fuel, by
the incorrect setting of the fuel feeding during reduce, etc. The limit for activating this error
can be set in the service menu and it is necessary to find an optimal setting when the boiler
is put into operation according to the type and quality of the fuel and according to the
structure of the heating system.
Low flue gas temperature B8 - when the boiler is in the mode “reduce”, not only the
difference between the flue gas temperature B8 and the water temperature at the boiler
outlet B2 are monitored. The minimum flue gas temperature B8 is monitored as well. If the
temperature values fall below this limit, the system reports an error and the boiler in the
mode “reduce is put out of operation. When this parameter is set, the real operating
parameters, the type and quality of fuel and other aspects must be taken into consideration.
Modbus error - it indicates the loss of communication of the converters of the oxygen
sensor and of the Climatix controller while using the modbus communication protocol RTU
(RS485).
Power supply of O2 sensor - error - it indicates an error in the power supply circuit of the
oxygen sensor. It is possible to try to correct this by the function “delete message” in the
menu of the oxygen sensor. If it does not help, it is necessary to replace either the
converter or the entire oxygen sensor.
O2 under 0.1% - it indicates that the oxygen sensor has measured the O2 concentration
lower than 0.1% for a longer time. This can result in damaging the sensor. This error can
also be a parallel effect of a failure in sensor heating or of an error in the modbus
communication.
PCB temperature - it indicates that the temperature of the converter of the oxygen sensor
is higher than 85°C. This means that the converter is overheated and it may be damaged.
The temperature 85°C represents the limit. The cause of this may be an inconvenient
installation of the converter which may be too close to the chimney body or the insufficient
natural cooling (based on selection of the dimension or material of the assembly box).
9. OTHER
59

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens Climatix 2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info