Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
Obj Object name Function Type/ length Flags
27 Cooling output
primary
0…100% 5.001
8 bit
CRT
Indicates the position of the cooling actuator of the first stage.
E.g. 2-pipe with electric heater application: Output of the cooling
coil
29 Enable electric
heating
Enable /
disable
1.003
1 bit
CWU
An electric heater can be disabled with this communication object
(e.g. to meet tariff regulations).
The same function is also available via local multifunctional input
X1/X2 (parameter P38, P40).
Only one input source must be used, either local input X1/X2 or
KNX bus.
30 Heating / cooling
changeover
Heat /
Cool
1.100
1 bit
CWU
Changeover information transmitted via bus.
Default: Current mode before power down.
The same function is also available via local multifunctional input
X1/X2 (parameter P38, P40).
Only one input source must be used, either local input X1/X2 or
KNX bus.
.
31 Application mode HVAC
control
mode
20.105
8 bit
CWU
0 Auto (default) Heating and/or cooling
1 Heat Heating only
2 Morning warmup* Heating only
3 Cool Cooling only
5 Precool* Cooling only
6 OFF Neither heating nor cooling
8 Emergency heat* Heating only
9 Fan only Fan runs at high speed
* Function handled like Heat (1) or Cool (3)
32 Enable fan
command value
Enable
Disable
1.003
1 bit
CWU
Set fan mode to Auto (disable) or Manual (enable) by a KNX
control unit. If Manual, the value received on
Fan command value
(34)
will be used to command the fan speed.
Default: Enable
The last interaction wins – either from the local fan mode button or
via bus.
33 Fan operation Auto
Manual
1.001
1 bit
CRT
Indicates the status of the fan mode: Auto (0) or Manual (1).
34 Fan command
value
0…100% 5.001
8 bit
CWU
The fan can be set to a specified speed by a KNX control unit
when manual fan operation is enabled.
Speed Fan command value (physical KNX value)
1 1...33% (1…85)
2 34…67% (86...170)
3 68…100% (171…255)
Fan speed “0” is not supported by the thermostat and the fan
speed will remain unchanged.
35 Fan output 0…100% 5.001
8 bit
CRT
Indicates the current fan speed as a value 0...100%
Speed Fan output (physical KNX value)
OFF 0% (0)
1 33% (84 )
2 66% (186)
3 100% (255)
36
37
38
Fan speed 1
Fan speed 2
Fan speed 3
ON
OFF
1.001
1 bit
CRT
Indicate the state of the relay outputs
Obj Object name Function Type/ length Flags
39
40
X1: Temperature
X2: Temperature
Temp .
value
9.001
2 Byte
CRT
Indicate the values of the temperature sensors connected to the
local inputs X1 / X2
41
42
X1: Digital
X2: Digital
ON
OFF
1.001
1 bit
CRT
Indicate the status of the digital inputs (adjusted by parameters
P39/P41) including considering of operating action
44 Outside
temperature
Temp .
value
9.001
2 Byte
CWU
The outside temperature measured by a KNX sensor can be
displayed on the thermostat, if parameter P07 "Additional user
information” is set = 2 (outside temperature).
45 Buttons left
ON/OFF
51 Buttons right
ON/OFF
ON
OFF
1.001
1 bit
CT
Switch control: Parameter ON/OFF functions = Top: ON; Bottom:
OFF
When pressing the button, the corresponding switching telegram is
sent immediately.
45 Button
top left: ON/OFF
ON
OFF
1.001
1 bit
CT
CWTU 1)
46 Button
bottom left: ON/OFF
51 Button
top right: ON/OFF
52 Button
bottom: Right
ON/OFF
Switch control: Parameter ON/OFF functions = 2 “ON/OFF”
functions.
When pressing the button, the corresponding switching telegram is
sent immediately: ON, OFF or Toggle.
1) If “Toggle” is selected, the communication object becomes
output and synchronization input
45
51
Buttons left:
ON/OFF
Buttons right:
ON/OFF
ON
OFF
1.001
1 bit
CT
47
53
Buttons left: Dim
up/down
Buttons right:
Dim up/down
Darker /
Brighter
1.001
4 bit
CT
On a short operation of the button, a switching telegram is sent,
e.g. press left top button: “On” is sent, press left bottom button:
“OFF” is sent.
When pressing the buttons longer, a dimming telegram is sent,
e.g. press left top button: “Brighter” is sent, press left bottom
button: “Darker” is sent.
On releasing the button, a “Stop” telegram is sent.
48
54
Buttons left:
Blind step/stop
Buttons right:
Blind step/stop
Step /
Stop
1.001
1 bit
CT
49
55
Buttons left:
Blind up/down
Buttons right:
Blind up/down
Up /
Down
1.001
1 bit
CT
On a short operation of the button, a telegram is sent to adjust the
louvers or stop the blinds if moving up or down.
On a long operation of the button, a telegram is sent to raise or
lower the blinds (up or down)
56

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RDF301 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RDF301

Siemens RDF301 Bedienungsanleitung - Deutsch - 2 seiten

Siemens RDF301 Bedienungsanleitung - Französisch - 2 seiten

Siemens RDF301 Installationsanweisung - Alle Sprachen - 2 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info