Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
3.12.2 Description of communication objects
Obj Object name Function Type/ length Flags
1 System time Time and
date
19.001
8 Byte
CWU
System time for display on the room thermostat. See parameter
P07 (3 or 4)
3 Time of day Time and
date
10.001
3 Byte
CWU
Another object for receiving the time of day for display on the room
thermostat. See parameter P07 (3 or 4)
4 Fault information Alarm
Info
219.001
6 Byte
CT
Common alarm output. If an alarm occurs, the alarm number is
transmitted
5 Fault state Faulty /
normal
1.005
1 bit
CT
Common alarm output. If an alarm occurs, the alarm flag is set
6 Fault
transmission
Enable /
disable
1.003
1 bit
CWU
A supervisor alarm system can disable the broadcasting of alarms
by the devices. This has no impact on the local display of alarms.
After a timeout of 48 hours, the sending of faults will automatically
be enabled again.
7 Room operating
mode:
Preselection
Auto
Comfort
PreComf.
Economy
Protection
20.102
1 Byte
CWTU
Controls the room operating mode selection of the thermostat via
bus.
The command can also be submitted as four 1-bit communication
objects (8...11). The last interaction wins – either from local
operating mode button or via bus.
Note: The thermostat will transform Precomfort either into
Economy or Comfort (selectable via P88).
8
9
10
11
Operating mode:
Preselection
Auto
Comf
Eco
Prot
Trigger 1.017
1 bit
CW
Switch room operating mode to either Auto, Comfort, Economy or
Protection.
The last interaction wins – either from the local operating mode
button or via bus.
12 Room operating
mode: Time
switch
Comfort
Economy
PreComf.
Protection
20.102
1 Byte
CWU
This information is provided by a central time switch or a
supervisor and defines the actual HVAC operating mode.
The command can also be submitted via three 1-bit
communication objects (13...15).
Protection has the highest priority and cannot be overridden.
Note: The thermostat will transform Precomfort either into
Economy or Comfort (selectable P88).
13
14
15
Time switch
Comfort
Economy
Protection
Trigger 1.017
1 bit
CW
Switch the HVAC mode to either Comfort, Economy or Protection
mode.
Obj Object name Function Type/ length Flags
16 Room operating
mode: State
Comfort
Economy
Protection
20.102
1 Byte
CRT
Effective room operating mode used by the thermostat
(considering time switch, user selection, window contact, etc.) This
state information is available via one 8-bit enumeration or three 1-
bit communication objects (17...19). Note: The thermostat does not
support Precomfort.
17
18
19
Room operating
mode:
State Comfort
State Economy
State Protection
ON
OFF
1.002
1 bit
CT
Corresponding communication object sends "True"
20 Window state Open
Closed
1.019
1 bit
CWU
The thermostat is set to Economy mode if value “1” (open) is
received. It switches back to the previous mode when the value is
“0” (closed).
"Window state" is sent e.g by a KNX switch or a KNX presence
detector. It has the same effect as the local operating mode
switchover contact X1, X2 (parameter P38, P40).
Only one input source must be used, either local input X1/X2 or
KNX bus.
21 Room
temperature
Temp .
value
9.001
2 Bytes
CRT
The value of the room temperature measured via built-in or
external sensor is available via this communication object.
22 Room tempera-
ture: Comfort
basic setpoint
Temp .
value
9.001
2 Bytes
CWU
If function "Temporary setpoint" is enabled via parameter P69, then
after an operating mode change, the setpoint adjustments made by
the user and via communication object 23 will be dismissed and
the thermostat will be reset to the Comfort basic setpoint.
Note: Setpoints that have been changed via the local HMI may be
overwritten during a system startup from a central master
controller, e.g.RMB795.
The Comfort basic setpoint is stored in EEPROM (see section
3.3.2).
The service life of the EEPROM depends on the number
of write cycles. Never write this communication object cyclically!
23 Room
temperature:
Comfort setpoint
Temp .
value
9.001
2 Bytes
CWTU
Communication object used to shift the setpoint used by the
thermostat (see section 3.3.2). Same priority as local setpoint shift
on the ther
mostat. The last intervention wins.
Note: The Comfort basic setpoint (object 22) will not be changed.
24 Current setpoint Temp .
value
9.001
2 Bytes
CRT
Current setpoint, including shift, compensation, etc., used by the
thermostat for temperature control
25 Heating output
primary
0…100 % 5.001
8 bit
CRT
Indicates the position of the heating actuator of first stage.
E.g. 2-pipe with electric heater application: Output of heating coil.
26 Heating output
secondary
0…100% 5.001
8 bit
CRT
Indicates the position of the heating actuator of the second stage.
E.g. 2-pipe with electric heater application: Output of the electric
heater.
55

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RDF600KN wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RDF600KN

Siemens RDF600KN Bedienungsanleitung - Deutsch - 2 seiten

Siemens RDF600KN Bedienungsanleitung - Holländisch - 2 seiten

Siemens RDF600KN Bedienungsanleitung - Französisch - 2 seiten

Siemens RDF600KN Installationsanweisung - Alle Sprachen - 2 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info