465406
7
Zoom out
Zoom in
Vorherige Seite
1/50
Nächste Seite
CE1G2205xx 2015-02-27 7/50
1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currentl1y acquired
blinks. Press
or to make a recalibration of max. ± 5 °C. To
save the entry, set the DIP switch to OFF and press the DIP switch
reset button (also refer to Fig.
).
1.1.2 Setpoint limitation: DIP switch 2
DIP switch ON: Setpoint limitation 16…35 °C
DIP switch OFF: Setpoint limitation 3…35 °C (factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON: Temperature display in °F
DIP switch OFF: Temperature display in °C (factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON: PID self-learning
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF: PID 6
For fast controlled systems, applications at locations with
great temperature variations.
DIP switch 4 OFF and 5 ON: PID 12
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF: 2-Point
For difficult controlled systems, 2-position controller with
a switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.5 Periodic pump run: DIP switch 6
Can only be used when circulating pump or valve is controlled!
This function protects the pump or valve against seizing during longer
off periods. Periodic pump run is activated for 3 minutes every 24
hours at 12:00 (display showing symbol ).
DIP switch ON: Periodic pump run on (also refer to Fig.
)
DIP switch OFF: Periodic pump run off (factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.6 Optimum start control: DIP switches 7 and 8
Optimum start control shifts switch on point P.1 such that the adjusted
setpoint will be reached at the required point in time. The setting
depends on the type of controlled system, that is, on heat transmission
(piping network, radiators), building dynamics (building mass,
insulation) and heat output (boiler output, flow temperature)
(also refer to graph in Fig.
/ 1.1.6).
DIP switch 7 ON and 8 ON:
1 h/°C For slow controlled systems
DIP switch 7 ON and 8 OFF:
¼ h/°C For fast controlled systems
DIP switch 7 OFF and 8 ON:
½ h/°C For medium controlled systems
DIP switch 7 OFF and 8 OFF:
OFF Off, no impact (factory setting)
Save the entry by pressing the DIP switch reset button.
Legend to graph in Fig. .
:
t Temperature (°C)
t Forward shift of switch on point (h)
TRx Actual value of room temperature
Pon Start point for optimum start control
1.1.7 Heating or cooling mode: DIP switch 9
DIP switch 9 ON:
Cooling mode
DIP switch 9 OFF:
Heating mode (factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.8 Radio clock: DIP switch 10
Can only be used with REV..DC (with integrated DCF77 receiver for
time signal from Frankfurt)!
DIP switch ON: Clock runs on built-in quartz
DIP switch OFF:
Time signal DCF77 from Frankfurt
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.9 DIP switch reset (Fig. )
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
2 Accessing the expert level
Move the selector slider to the RUN position and press simultaneously and for 3 seconds, then release the buttons and, within 3 seconds,
press simultaneously
and for 3 seconds, release and keep depressed for another 3 seconds. This enables you to access the expert
level for making the settings on that level. on display (also refer to Fig. G).
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with and . Confirm the
settings by pressing
.
The expert level is quit by pressing the operating mode selection button .
Code list
Function block Code Name Factory setting Your setting
Basic settings
00 Language English
01 Sensor calibration off
02 Switching differential 2-point 0.5 °C
LCD settings
10 Illumination time 10 seconds
11 Background brightness 0
12 Contrast 0
Clock settings
30
Time zone
Deviation from time signal received from
Frankfurt (Central European Time CET)
(refer to Note 1)
0 hours
31 Start of summer time (refer to Note 2) March 31 (31-03)
32 End of summer time (refer to Note 3) October 31 (31-10)
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
DA
TR
EL
7

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

siemens-rev24

Suche zurücksetzen

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens REV24 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens REV24

Siemens REV24 Bedienungsanleitung - Deutsch - 2 seiten

Siemens REV24 Bedienungsanleitung - Englisch - 14 seiten

Siemens REV24 Bedienungsanleitung - Holländisch - 2 seiten

Siemens REV24 Bedienungsanleitung - Französisch - 2 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info